Issue Number: 1
Figure 8-16 Roping Ratio
Nominal Elevator Speed rpm (E07) is calculated automatically when Nominal Elevator Speed (E01), or Sheave Diameter (E02), or Roping (E03), or
Gearbox Ratio Numerator (E04), or Gear Ratio Denominator (E05) are modified.
See Nominal Elevator Speed rpm (E07) for more details.
This sets the gearbox ratio numerator and is used to calculate Nominal Elevator Speed rpm (E07). A gear box ratio (In:Out) of 7:3 is entered as 7 in
Gearbox Ratio Numerator (E04).
Nominal Elevator Speed rpm (E07) is calculated automatically when Nominal Elevator Speed (E01), or Sheave Diameter (E02), or Roping (E03), or
Gearbox Ratio Numerator (E04), or Gear Ratio Denominator (E05) are modified.
The default gearbox ratio of 1:1 is used for gearless PM motor applications.
See Nominal Elevator Speed rpm (E07) for more details.
This sets the gearbox ratio numerator and is used to calculate Nominal Elevator Speed rpm (E07). A gear box ratio (In:Out) of 7:3 is entered as 3 in
Gear Ratio Denominator (E05).
Nominal Elevator Speed rpm (E07) is calculated automatically when Nominal Elevator Speed (E01), o
r
Sheave Diameter (E02), or Roping (E03), or
Gearbox Ratio Numerator (E04), or Gear Ratio Denominator (E05) are modified.
The default gearbox ratio of 1:1 is used for gearless PM motor applications.
See Nominal Elevator Speed rpm (E07) for more details.
E04 Gearbox Ratio Numerator
Mode Open-Loop, RFC-A, RFC-S
Minimum 1 Maximum 32767
Default
Open-Loop, RFC-A: 31
RFC-S: 1
Units
Type 16 Bit User Save Update Rate Background
Display Format Standard Decimal Places 0
Coding RW
E05 Gear Ratio Denominator
Mode Open-Loop, RFC-A, RFC-S
Minimum 1 Maximum 32767
Default 1 Units
Type 16 Bit User Save Update Rate Background
Display Format Standard Decimal Places 0
Coding RW