User Menu A Commissioning
Advanced
Parameters
Diagnostics Optimization CT MODBUS RTU Technical Data
268 E300 Design Guide
Issue Number: 1
Mode: Open-Loop, RFC-A, RFC-S
The bits in the IO Status Word (F01) each correspond with one digital I/O as shown below. The update rate of the individual bits in these registers
differs depending upon the I/O.
The IO Status Word (F01) is always active and shows the value in the Digital I/O State parameter for all digital I/O configured as inputs.
See T24 Digital I/O 01 State (F03).
The Digital I/O State parameter shows the state of digital I/O on the drive. All I/O except Digital Input 11 (Keypad Run Button), Digital Input 12 (Keypad
Auxiliary Button), Digital Input 13 (24 V Supply Input) and Digital Input 14 (Keypad Stop Button) use IEC61131-2 logic levels. As default the inputs use
positive logic, and so the state parameter is 0 if the digital I/O is low or 1 if the digital I/O is high. Input Logic Polarity (F02) can be set to zero to change
F01 IO Status Word
Mode Open-Loop, RFC-A, RFC-S
Minimum
0
(Display: 0000000000000000)
Maximum
65535
(Display: 1111111111111111)
Default Units
Type 16 Bit Volatile Update Rate 250 µs write
Display Format Binary Decimal Places 0
Coding RO, PT, BU
DI/O Bit Function
Bit update rate
Input Register Output Register Output Enable Register
1 0 Digital Input/Output 2 ms 250 µs Background
2 1 Digital Input/Output 2 ms 250 µs Background
3 2 Digital Input/Output 2 ms 2 ms Background
4 3 Digital Input 250 μs Not applicable Not applicable
5 4 Digital Input 250 μs Not applicable Not applicable
6 5 Digital Input 2 ms Not applicable Not applicable
7 6 Relay Output Bit always 0 2 ms Background
8 7 24 V Supply Output Bit always 0 2 ms Background
9 8 Safe Torque Off 1 2 ms Not applicable Not applicable
10 9 Safe Torque Off 2 2 ms Not applicable Not applicable
11 10 Keypad Run Button Background Not applicable Not applicable
12 11 Keypad Auxiliary Button Background Not applicable Not applicable
13 12 24 V Supply Input 2 ms Not applicable Not applicable
14 13 Keypad Stop Button Background Not applicable Not applicable
15 14 Relay 2 Output Bit always 0 2 ms Background
F02 Input Logic Polarity
Mode Open-Loop, RFC-A, RFC-S
Minimum 0 Maximum 1
Default 1 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, TE, BU
Value Text
0 Negative Logic
1 Positive Logic
F03 T24 Digital I/O 01 State
Mode Open-Loop, RFC-A, RFC-S
Minimum 0 Maximum 1
Default Units
Type 1 Bit Volatile Update Rate 2 ms write
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT