Safety 
information
Product 
information
Mechanical 
installation
Electrical 
installation
Getting 
started
User Menu A Commissioning
Advanced 
Parameters
Diagnostics Optimization CT MODBUS RTU Technical Data
28 E300 Design Guide
          Issue Number: 1
Table 2-30 Emissions compliance
The limits in the table are based on the ratios of the specific harmonics to the rated fundamental current (In / I1 in clause 6.7.2 of EN 12015:2004).
2.13.2     Immunity - EN 12016
The standard gives immunity requirements over a range of standard immunity test methods. Generally these correspond to the tests required by the
generic standards for the residential and industrial environments, EN 61000-6-1 and EN 61000-6-2. However there are more severe test levels 
prescribed for safety circuits. In the tests for safety circuits, the drive is permitted to trip but the safety function must continue to operate.
The following table shows the status of the whole range of drives covered by this data sheet.
Table 2-31 Immunity compliance
* Suppression is not required to ensure safety, and is generally not required. Control Techniques recommends that the suppression be installed if the 
lines connected to the port exceed 30 m in length, based on the requirements of EN 61000-6-2. See section 4.17.8 Surge immunity of control 
circuits on page 103.
Item Limit (%) Typical (%)
Harmonic:
5 30 27.6
7187.9
11 13 6.4
13 8 3.7
THD 35 29.9
PWHD 39 16.5
cosφ
0.9790
Distortion factor
0.9580
Power factor
0.9379
Test Status – drive functions Status – Safe Torque Off used in safety circuits
Electrostatic discharge  Conform Electrostatic discharge Conform 
Radio frequency electromagnetic field  Conform Conform (the drive might trip but no loss of safety function)
Fast transients common mode – to
signal and power ports 
Conform Conform
Surge:
Signal and control lines 
Conform Conform (External suppression is required to prevent trip or damage)*
Power ports  Conform Conform
Radio frequency common mode – to
signal and power ports 
Conform Conform
Voltage dips  Conform Conform
Voltage interruptions  Conform Conform