E300 Design Guide 283
Issue Number: 1
T8 Analog Input 3 Thermistor Feedback (F62) shows the measured resistance.
If a KTY84, PT100, PT1000 or PT2000 type device is selected for temperature feedback then T8 Analog Input 3 Thermistor Temperature (F63) shows
the temperature of the device based on the resistance to temperature characteristic specified for this device. Otherwise T8 Analog Input 3 Thermistor
Temperature (F63) = 0.0.
T9 Analog Output 1 Source (F64) defines the source parameter for analog output 1. The value of the source parameter is scaled with T9 Analog
Output 1 Scaling (F65) and if the scaling is greater than 1.000 the value is clamped between -100 % and +100 % or between 0 % and 100 %
depending on whether the output is bipolar or unipolar. The resulting value is then used to control the output. It should be noted that the normal rules
for parameter routing do not apply, but the scaling always makes -100 % to +100 % correspond to the range from minus source parameter maximum
to plus source parameter maximum, and 0 % corresponds to the source parameter value of zero. This means for example that a parameter with a
minimum of 1 and a maximum of 10 will produce an output that changes from 10 % to 100 % as the parameter is change from minimum to maximum.
The outputs provided with different hardware are given in the table below.
The output mode is defined by T9 Analog Output 1 Mode (AU21) as shown in the table below.
See T9 Analog Output 1 Source (F64).
F62 T8 Analog Input 3 Thermistor Feedback
Mode Open-Loop, RFC-A, RFC-S
Minimum 0 Maximum 5000
Default Units Ω
Type 16 Bit Volatile Update Rate Background write
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
F63 T8 Analog Input 3 Thermistor Temperature
Mode Open-Loop, RFC-A, RFC-S
Minimum -50 Maximum 300
Default Units °C
Type 16 Bit Volatile Update Rate Background write
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
F64 T8 Analog Output 1 Source
Mode Open-Loop, RFC-A, RFC-S
Minimum A00 Maximum AB99
Default A00 Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Menu Param Alpha Numeric Decimal Places 3
Coding RW, PT, BU
Internal IO Identifier (J66) Analog Output 1 Analog Output 2
0: Standard Analog and Digital I/O Bipolar Voltage Bipolar Voltage
T9 Analog Output 1 Mode (AU21) Standard Analog and Digital I/O
Volt -10 V to + 10 V
0-20 mA Not possible
20-0 mA Not possible
4-20 mA Not possible
20-4 mA Not possible
F65 T9 Analog Output 1 Scaling
Mode Open-Loop, RFC-A, RFC-S
Minimum 0.000 Maximum 10.000
Default 1.000 Units
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 3
Coding RW