Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
User Menu A Commissioning
Advanced
Parameters
Diagnostics Optimization CT MODBUS RTU Technical Data
286 E300 Design Guide
Issue Number: 1
When set to 0, a thermistor input is not selected, and T8 Analog Input 3 Mode (F52) is set to Volt or 6.
When set to 1, analog input 3 thermistor input is selected, and T8 Analog Input 3 Mode (F52) is set to Therm No Trip or 9. T8 Analog Input 3
Thermistor Type (F59), T8 Analog Input 3 Thermistor Trip Threshold (F60) and T8 Analog Input 3 Thermistor Reset Threshold (F61) are used to
configure the thermistor input.
When set to 2, the drive encoder thermistor input is selected, and T8 Analog Input 3 Mode (F52) is set to Volt or 6. Encoder Thermistor Type (F69),
Encoder Thermistor Trip Threshold (F70) and Encoder Thermistor Reset Threshold (F71) are used to configure the thermistor input.
F74 Motor Thermistor Input Select
Mode Open-Loop, RFC-A, RFC-S
Minimum 0 Maximum 2
Default Units
Type 16 Bit User Save Update Rate Background
Display Format Standard Decimal Places 0
Coding RW