The nominal output cable size assumes the motor maximum current matches that of the drive. Where a motor of reduced rating is used the cable
rating may be chosen to match that of the motor. To ensure that the motor and cable are protected against over-load, the drive must be programmed
with the correct motor rated current.
Ensure cables used suit local wiring regulations.
4.12.1 Cable type
Use 105 °C (221 °F) (UL 60/75 °C (temp rise) PVC-insulated cable with copper conductors having a suitable voltage rating, for the following power
connections:
• AC supply to external EMC filter (when used)
• AC supply (or external EMC filter) to drive
• Drive to motor
• Drive to braking resistor
Most cables have an insulating jacket between the cores and the armor or shield; these cables have a low capacitance and are recommended.
Table 4-13 Cable ratings (200 V)
The nominal cable sizes below are only a guide. The mounting and grouping of cables affects their current-carrying capacity, in some cases
smaller cables may be acceptable but in other cases a larger cable is required to avoid excessive temperature or voltage drop. Refer to
local wiring regulations for the correct size of cables.
Model
Cable size (IEC)
mm
2
Cable size (UL)
AWG
Input Output Input Output
Nominal Maximum Installation Nominal Maximum Installation Nominal Maximum Nominal Maximum
03200050
1.5
4B2
1.5
4B2
14
10
14
10
03200066
03200080
44
12 12
03200106
04200137
6
8B2
6
8B2
10
8
10
8
04200185
8
888
05200250
10
10 B2 10 10 B2 8 8 8 8
06200330
16
25 B2
16
25 B2
4
3
4
3
06200440
25
25 3 3
07200610
35
70 B2
35
70 B2
2
1/0
2
1/007200750 11
07200830
70
70 1/0 1/0