1592025700 IPROFAMILY 3.5 stp GB 2016.12.07 iPro Series 22/96
Out1 - Out4: ±2% full scale
Out5 – Out6: ±2% full scale
The electrical devices controlled by these analogue outputs must be
powered separately with another transformer (do not use the same
secondary of the controller's power) in order to prevent the outputs from
malfunctioning or being damaged.
4.2.3.4 Digital outputs
10 or 15, depending on the model
Type of output:
(configurable via software parameter)
Relays with normally open contact
Verify the capacity of the output used. There is double insulation between
the digital outputs and the low voltage of the rest of the circuit.
Do not use different voltages for the various groups of relays nor within
4.2.3.5 Wiring diagrams