Powerdrive F300 User Guide 245
Issue Number: 2
Table 12-14 AC Input current and fuse ratings (200 V)
Fuses
The AC supply to the drive must be installed with suitable protection against overload and short-circuits. Table 12-14 to Table 12-17 shows
the recommended fuse ratings. Failure to observe this requirement will cause risk of fire.
Model
Typical
input
current
Maximum
continuous
input current
Maximum
overload
input
current
Fuse rating
IEC UL / USA
Nominal Maximum
Class
Nominal Maximum
Class
AA AAA A A
03200066
8.2
10.4
15.8
16
25 gG
20
25 CC, J or T**
03200080
9.9
12.6
20.9
20
03200110
14
17
25
25
03200127
16
20
34
25
04200180
17
20 30 25 25
gG
25 25
CC, J or T**
04200250
23
28 41 32 32 30 30
05200300
24
31 52 40 40 gG 40 40 CC, J or T**
06200500
42
48 64
63 63 gG
60
60 CC, J or T**
06200580
49
56 85 60
07200750
58
67 109 80 80
gG
80 80
CC, J or T**07200940
73
84 135 100 100 100 100
07201170
91
105 149 125 125 125 125
08201490
123
137 213
200 200 gR
200 200
HSJ
08201800
149
166 243 225 225
09202160
172
205 270 250 250
gR
250 250
HSJ
09202660
228
260 319 315 315 300 300
10203250
277
305 421 400 400
gR
400 400
HSJ
10203600
333
361 494 450 450 450 450