93
Reference Manual
00809-0100-4840, Rev CB
Appendix B: Product Certifications
February 2015
Product Certifications
B.4 Hazardous locations certifications
B.4.1 American and Canadian certifications
Factory Mutual (FM) intrinsically safe and non-incendive
approvals (on the 3105 only)
I5 Project ID: 3024095
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D
Zone Marking: Class I, Zone 0, AEx ia IIC
Non-incendive for Class I, Division 2, Groups A, B, C and D
Zone Marking: Class I, Zone 2, AEx nA IIC
Temperature Code: T6 (T
a
= 55 °C)
Temperature Code: T4 (T
a
= 60 °C)
Control Drawing: 71097/1216 (See Figure B-1 on page 98)
Ui = 30 V, li = 120 mA, Pi = 0.82 W, Li = 108 H, Ci = 0 F
Canadian Standards Association (CSA) intrinsically safe and
non-incendive approvals (on the 3105 only)
I6 Project ID: 02 CSA 1352094
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D.
Zone Marking: Class I, Zone 0, Ex ia IIC
Non-incendive for Class I, Division 2, Groups A, B, C and D.
Zone Marking: Class I, Zone 2, Ex nL IIC
Temperature Code: T4 (T
a
= –40 to 60 °C)
Temperature Code: T6 (T
a
= –40 to 55 °C)
Control Drawing: 71097/1218 (See Figure B-2 on page 99)
Ui = 30 V, li = 120 mA, Pi = 0.82 W, Li = 108 H, Ci = 0 F
B.4.2 European certification
ATEX intrinsically safe approval (on the 3105 only)
I1 Certificate: Sira 06ATEX2260X
ATEX Intrinsic Safety
II 1 G, Ex ia IIC T6 Ga (T
a
= –40 to 55 °C), Ex ia IIC T4 Ga (T
a
= –40 to 60 °C)
Ui = 30 V, li = 120 mA, Pi = 0.82 W, Li = 108 H, Ci = 0 F
(see “Instructions specific to hazardous area installations (I1 and I7)” on page 95)
Potential electrostatic charging hazard: to prevent the risk of electrostatic sparking, the
surface of the glass-filled nylon (plastic) enclosure should only be cleaned with a damp
cloth. Do not directly install in any process where its enclosure might be charged by the
rapid flow of non-conductive media.
The aluminum alloy (metal) enclosure presents a risk of ignition due to impact and shall be
taken into consideration during installation and use.
Refer to the housing label to identify the approvals for your transmitter.