CG Drives & Automation 01-7492-01r1 159
AnOut1 Function Min [5334]
With AnOut1 Function Min the physical minimum value is
scaled to selected presentation. The default scaling is
dependent of the selected function of “AnOut1 [531]”.
Table 38 shows corresponding values for the min and max
selections depending on the function of the analogue output
[531].
*) Fmin is dependent on the set value in menu
“Minimum Speed [341]”.
Example
Set the AnOut function for Motorfrequency to 0Hz, set
AnOut functionMin [5334] to “User-defined” and AnOut1
VaMin[5335] = 0.0. This results in an anlogue output signal
from 0/4 mA to 20mA: 0Hz to Fmot.
This principle is valid for all Min to Max settings.
AnOut1 Function Value Min [5335]
With AnOut1 Function VaMin you define a user-defined
value for the signal. Only visible when user-defined is
selected in menu [5334].
AnOut1 Function Max [5336]
With AnOut1 Function Max the physical minimum value is
scaled to selected presentation. The default scaling is
dependent on the selected function of AnOut1 [531]. See
Table 38.
AnOut1 Function Value Max [5337]
With AnOut1 Function VaMax you define a user-defined
value for the signal. Only visible when user-defined is
selected in menu [5334].
AnOut2 Function [534]
Sets the function for the Analogue Output 2.
5334 AnOut1FcMin
Default: Min
Min 0 Min value
Max 1 Max value
User defined 2 Define user value in menu [5335]
Ta b l e 3 8
AnOut
Function
Min Value Max Value
Process Value Process Min [324] Process Max [325]
Speed Min Speed [341] Max Speed [343]
Torque 0% Max Torque [351]
Process Ref Process Min [324] Process Max [325]
Shaft Power 0% Motor Power [223]
Frequency Fmin * Motor Frequency [222]
Current 0 A Motor Current [224]
El Power 0 W Motor Power [223]
Output
Voltage
0 V Motor Voltage [221]
DC voltage 0 V 1000 V
AnIn1
AnIn1 Function
Min
AnIn1 Function Max
AnIn2
AnIn2 Function
Min
AnIn2 Function Max
AnIn3
AnIn3 Function
Min
AnIn3 Function Max
AnIn4
AnIn4 Function
Min
AnIn4 Function Max
5335 AnOut1VaMin
Default: 0.000
Range: -10000.000–10000.000
5336 AnOut1FcMax
Default: Max
Min 0 Min value
Max 1 Max value
User defined 2 Define user value in menu [5337]
NOTE: It is possible to set AnOut1 up as an inverted
output signal by setting AnOut1 Min > AnOut1 Max.
See fig. 127, page 152.
5337 AnOut1VaMax
Default: 0.000
Range: -10000.000–10000.000
534 AnOut2 Fc
Default: Torque
Selection: Same as in menu
[531]