Proline Promag 55 PROFIBUS DP/PA Commissioning
Endress+Hauser 77
Performing the "Pulsating Flow" Quick Setup
This Quick Setup menu guides you systematically through the setup procedure for all the device
functions that have to be modified and configured for measuring pulsating flows. Note that this has
no effect on values configured beforehand, such as measuring range, current range or full scale
value.
A0004615-EN
Fig. 55: Quick Setup for measuring severely pulsating flows.
Recommended settings: see next page.
!
Note!
The display returns to the cell PULSATING FLOW QUICK SETUP (1003) if you press the Q key
combination during parameter interrogation.
You can call up the Setup menu either directly from the "COMMISSIONING" Quick Setup menu
or manually by means of the function PULSATING FLOW QUICK SETUP (1003).
+
+
E
+
E
4200
4225
8005
6400
6402
6403
6404
4206
4208
4004
4005
B
2002
1003
Esc
E
+
-
XXX.XXX.XX
Yes No
Current output 1 Freq.-/Pulse output 1
Selection of output type
Quit
Frequency Pulse
Operation mode
Measuring mode
Alarm delay
Assign
LF-Cut off
On-value
LF-Cut off
Off-value
LF-Cut off
Pressure
shock suppression
Quit
Quick Setup
Measuring mode
Time constant
Measuring mode
Time constant
Quick Setup
HOME-POSITION
Display
damping
Pulsating flow
Configure another output ?
m Only the output not yet configured in the current Setup is offered for selection in the second cycle.
n The "YES" option remains visible until both outputs have been configured. "NO" is the only option displayed when
no further outputs are available.