Commissioning Proline Promag 55 PROFIBUS DP/PA
78 Endress+Hauser
Quick Setup "Pulsating Flow"
HOME position F MEASURAND O QUICK SETUP N PULSATING FLOW QS (1003)
Function No. Function name Selection with OS
To the next function with F
1003 QS PULS. FLOW YES
After F is pressed by way of confirmation, the
Quick Setup menu calls up all the subsequent
functions in succession.
Basic configuration
2002 DISPLAY DAMPING 3 s
Signal type for "CURRENT OUTPUT 1"
4004 MEASURING MODE PULS. FLOW
4005 TIME CONSTANT 3 s
Signal type for "FREQ./PULSE OUTPUT 1" (for FREQUENCY operating mode)
4206 MEASURING MODE PULS. FLOW
4208 TIME CONSTANT 0 s
Signal type for "FREQ./PULSE OUTPUT 1" (for PULSE operating mode)
4225 MEASURING MODE PULS. FLOW
Other settings
8005 ALARM DELAY 0 s
6400 ASSIGN LOW FLOW CUTOFF VOLUME FLOW
6402 ON-VALUE LOW FLOW CUTOFF Recommended setting:
A0004432-EN
*Full scale values ä 18
6403 OFF-VALUE LOW FLOW CUTOFF 50%
6404 PRESSURE SHOCK SUPPRESSION 0 s
Back to the HOME position:
Press and hold down Esc keys X for longer than three seconds or
Repeatedly press and release Esc keys X Exit the function matrix step by step
1000
On-value
max. full scale (per DN)*