Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP
200
Diagnostic information Remedy instructions Coding of diagnostic
information (hex)
No. Short text
372 Sensor electronic (ISEM) faulty 1. Restart device
2. Check if failure recurs
3. Replace sensor electronic module
(ISEM)
• 0x10000A1
• 0x10000C7
• 0x10000C9
• 0x10000D4
• 0x10000DA
• 0x1000120
• 0x10002CB
• 0x10002CC
• 0x10002CD
• 0x10002CE
• 0x10002CF
• 0x10002D0
Status signal F
Diagnostic behavior Alarm
Diagnostic information Remedy instructions Coding of diagnostic
information (hex)
No. Short text
373 Sensor electronic (ISEM) faulty 1. Transfer data or reset device
2. Contact service
0x10002D1
Status signal F
Diagnostic behavior Alarm
Diagnostic information Remedy instructions Coding of diagnostic
information (hex)
No. Short text
374 Sensor electronic (ISEM) faulty 1. Restart device
2. Check if failure recurs
3. Replace sensor electronic module
(ISEM)
0x80000CE
Status signal S
Diagnostic behavior [from the
factory]
1)
Warning
1) Diagnostic behavior can be changed.
Diagnostic information Remedy instructions Coding of diagnostic
information (hex)
No. Short text
375 I/O- 1 to n communication failed 1. Restart device
2. Check if failure recurs
3. Replace module rack inclusive
electronic modules
0x1000107
Status signal F
Diagnostic behavior Alarm
Diagnostic information Remedy instructions Coding of diagnostic
information (hex)
No. Short text
382 Data storage 1. Insert T-DAT
2. Replace T-DAT
0x100016D
Status signal F
Diagnostic behavior Alarm