4 Electrical installation
38 Festo – GDCP-CMMP-M0-HW-EN – 1511c – English
To release the holding brake, care must be taken to maintain the voltage tolerances at the
holding brake connection terminals.
Also observe the specifications in Tab. A.4 è Page 66.
It may be necessary to insert a relay between the device and the holding brake, as shown in
Fig. 4.5è Page 38:
CMMP-AS-...-M0
BR+
Br-
Resistor and
Capacitor for
Spark arresting
+24V power pack
GND power pack
+24V brake
GND brake
Motor
Free-wheeling diode
Fig. 4.5 Connecting a high-current holding brake to the device
High voltages with spark formation are created when inductive direct currents are con
nected via relays. For interference suppression, we recommend integrated RC interfer
ence suppressors, e.g. from Evox RIFA, designation: PMR205AC6470M022 (RC element
with 22 Ω in series with 0.47 μF).