2. Commissioning
2-64
Festo P.BE-CPX-PNIO-E N en 1407c English
2.10 Configuration in the Remote Controller operating mode
If there is a control block in your CPX terminal, you must op-
erate the bus node in the Remote Controller operating mode.
The bus node then occupies 8 or 16 input bytes and 8 or
16 output bytes (dependent on the switch position DIL 2.2
Tab. 1/4). These are available to the control program in
the control block CPX-FEC or CPX-CEC and to the PROFINET
Master.
Configuration of the Re-
mote Controller operating
mode bus node
1. Ensure that DIL switches of the control block are in the
“Remote Controller” position ( Description
P.BE-CPX-FEC or P.BE-CPX-CEC).
2. Ensure that DIL switch 1 of the bus node is in the “Re-
mote Controller” position ( Section 1.4.2, Tab. 1/1).
– DIL 1.1: ON
– DIL 1.2: OFF
3. Set the required data field size with DI L switch 2,
(see Tab. 1/4).
4. Start the configuration and programming software of your
control system, e.g. Siemens STEP 7.
5. Open the hardware confi guration, e.g. “HW Config”.
6. If yo u change an existing confi guration: If necessary, re-
move the existing bus nodes and all other (subordinate)
modules from this CPX terminal configuration.
7. Carry out the bus node selection (station selection) with
the station type CPX RC or CPX-RC-FO (see section 2.7.1).
8. Select the required data field size in the configuration and
programming software:
8bytesI/8bytesO...16bytesI/16bytesO.