2. Commissioning
2-47
Festo P.BE-CPX-PNIO-EN en 1407c English
Note
The DIL switch settings for operating mode and dia-
gnostics mode must match the bus node selection in the
context of a PLC hardw are and network confi guration (see
Tab. 1/3 and section 2.6.2).
•
Check the setting of the DIL switches for operating mode
and diagno sti cs mode (see sectio n 1.4.2): Make sure
that the setting for operating mode and diagnostics
mode selected on the bus node via DI L switch agrees
with the function of the catal o gue element.
2.7.2 Modify I/O address
1. Double click on the module name in the configuration
table.
The “Properties – ...” window is displayed.
2. Select the “Addresses” tab.
3. Change the start address (“Start”) of the inputs or out-
puts.
4. Confirm the input with “OK”.
The modified address is displayed in the configuration
table.
2.7.3 Modify diagnostics ad dress
The diagnostics address is automatical l y assigned by the
Siemens STEP 7 configuratio n and programming software -
HW Config. A change is rarely required.
1. Double-click on “Slot 0” in the configuration table.
The “Properties – CPX” window is displayed
(see Fi g. 2/12).