EasyManua.ls Logo

FireClass 500 - Connecting System Devices

FireClass 500
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-NAC FIRE+
Type C output (EN54-1). - Silenceable,
Bypassable (Disabled), Supervised
—— Terminals
for supervised devices activated by positive (24 V):
Ø
During ALARM status —— positive (27.6 V) on ter
-
minal [+]; negative on terminal [-].
Ø
During STANDBY status —— negative on terminal
[+]; positive (27.6 V) on terminal [-].
Ø
This output can be bypassed via the DISABLE menu.
ALARM status will activate this non-programmable out
-
put.
[12V] [M]
Auxiliary power 12 V . Power supply to de
-
vices that operate at 12V (powered by the standby bat
-
teries and protected by self recover termic fuse):
Ø Positive (13.8 V) on terminal [12V];
Ø Negative on terminal [M].
Max current on terminal [12V] must not exceded
200mA.
NAC1 NAC2 and NAC3
Supervised/Silencea
-
ble/Bypassable (Disabled) Programmable Alarm
Outputs.
These Outputs are for the Alarm signalling devices.
Operating principles:
Ø in Standby status, these Outputs will be INACTIVE
(read on for details);
Output INACTIVE: negative pull-down to 0 V on [+] termi-
nal; positive pull-up to 27.6 V on the [–] terminal.
Output ACTIVE: positive pull-up to 27.6 V on the [+] ter-
minal; negative pull-down to 0 V on the [–] terminal.
Ø NAC1, NAC2 and NAC3 will restore to standby when
the Control panel Resets.
Ø NAC1, NAC2 and NAC3 can be Silenced (forced to
standby).
The NAC Outputs will hold standby status for the pro
-
grammed Silence Time. If Alarm conditions are pre
-
sent when the programmed Silence Time expires,
they will re-activate.
+
NAC1, NAC2 and NAC3 accept devices that ope
-
rate within SELV limits ONLY.
+
EN54-2 cerification applies ONLY when, NAC1,
NAC2, NAC3, OS1, OS2, OS3, OS4, OS5, OS6,
OS7, OS8, O9, O10, O11, O12, O13, O14, O15,
O16 and RELAY FIRE outputs are not C , E , J , G
(EN 54-1) type,
therefore these outputs MUST NOT UTILIZED to
manage Fire Alarm devices and/or Fire Alarm
Transmission devices and/or Fire Fault Transmis
-
sion devices and/or Automatic Fire Alarm Systems.
The System Wiring
+
Use shielded cable only for all connections, with
one end of the shield connected to the Control pa
-
nel negative terminal and the other left free.
!
High Voltage leads (110/230 V) must be bun
-
ched separately from Low Voltage leads (24 V).
All leads must be bunched in such a way as to
avoid contact with other wiring and compo
-
nents.
n
Connecting Addressable Analogue Devices
The control panel has 2 loops for addressable analogue
devices.
Each loop supports 250 addressable analogue fire de
-
tectors and ananalogue devices (Input modules, Con-
ventional Zone modules, Output modules).
+
Every detector and every module connected to a
loop must be assigned a DIFFERENT address
(using the special Loop Service Tool FC490ST)
from the other detectors on the same loop.
You can use 2 or 4 wires for the loop connections.
NOTE: The loop connection type must be specified du
-
ring the programming phase.
Figure 9(1) illustrates the 2-wire connection to Loop2.
Figure 9(2) illustrates the 4-wire connection to Loop2.
+
Whatever the type of connection performed, make
sure that any short circuit or open circuit in the wi
-
ring does not lead to the loss of more than 32
detectors. An insulator should be fitted at least
every 32 detectors
INSTALLATION 21
Osx
27,6V
FireC lass
1N4007
LOAD
27K
SUPERVISED
Figure 8 OSx Outputs connecting

Table of Contents

Related product manuals