FireClass 500 - Key 8-System; FC500 REP Repeater Address from the Repeater Panel ONLY; NETWORK Configuration

FireClass 500
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
KEY 8-SYSTEM
The option SYSTEM in the programming menu activa
-
tes the system language selection page.
+
Other language pairs may be loaded from software
in this phase:
Alphanumeric keypad No function is related to the
Alphanumeric keypad.
Cursor Keys
No function is related to UP Key;
No function is related to Down Key;
Use the Righ key to select the next language.
Use the Left key to select the previous language.
ESC Key
Use ESC key to cancel the operation and to
step back to previous page.
ENTER Key
ENTER Key accepts the selection.
Function Keys
No function is related to F1, F2, F3, F4
keys.
FC500REP Repeater Address
from the Repeater panel ONLY
After the FC500 control panel has been connected, at
the first start-up the FC500REP will verify the presence
of the address and its conformity. If the address is cor-
rect, the Repeater will start to work; on the contrary
the display will ask to insert a new address; the display
of Figure 50 will be shown; in this phase:
Alphanumeric keypad Use the alphanumeric keypad
to insert the address of 1 digit.
Cursor Keys
No function is related to UP, Down,
Right, Left Keys.
ESC Key
Use ESC key to cancel the operation and to
step back to previous page.
Tasto ENTER Use the ENTER Key to confirm the ad
-
dress.
Function Keys
No function is related to F1, F2, F3, F4
keys.
+
If for any reason the address of a repeater is chan
-
ged by mistake, the system will show the message
of the Figure 51, in this case the address of the re
-
peater will be changed using the ESC key.
NETWORK Configuration
Two ways are available to enrol the Network:
first:
1- the Master Control panel can do the Enrolling (autolear-
ning) after one or more Slave Control panels and one or
more Repeaters have been enabled in the network (see
previous paragraphs);
1a-usethe
1 Key to enroll (see page 47);
1b- use the "Upload from board" key (Software FireClass500
console) in the Master control panel;
second:
2- Use the Software (FireClass500 console) to insert one
or more Slave Control panels (from Master control panel);
2a- Use the "General Options" section (FireClass500 con
-
sole) in every Slave control panels to enable the Slave pa
-
nel in the network;
2b- Use the "General Options" section (FireClass500
console) in the Master control Panel to enable the Slave
Control panels, the Repeaters and the Master control pa
-
nel itself in the network .
2c- Use the " Download to board" key.
After the "Auto" Enrolling the system configure the Net
-
work devices (Slave control panels and Repeaters) and
besides the Loop devices.
At the end of the "Auto" Enrolling, the "Master" control
panel can manage the "Slave" control panels and the
Repeaters.
PROGRAMMING FROM THE PANEL 51
!!FAULT!!
Serial link is down
unable to communicate with the system
press ESC to change repeater address
Figure 49 Display "the repeater link is down"
System lev.3: PROGRAM
Access level
This symbol shows the presence
of the connection between the
User interface and the main Board.
The symbol KO will be shown
when the connection fails.
Control panel Status
Language choise
ITA eng
LANGUAGE
^
Master Panel
Figure 50 Page to select the language of the system
FC500REP REPEATER
Insert the number of the address [1-8]
[_]
Space to insert the address
This symbol shows the presence
of the connection between the
FC500REP repeater the Master
Control Panel and the relative
address.
Figure 51 Display to insert a new FC500REP address