EasyManua.ls Logo

FireClass 500 - Accessory; FC500 IP - IP Module; FC500 PSTN - Telecom Module; Universal Base

FireClass 500
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACCESSORY
The following is a list of accessories for control panel in
the FC500 series, with a description of the main featu
-
res. For further information about these accessories,
please refer to the instructions supplied with the acces
-
sories themselves or download them from the FireClass
website: http://www.fireclass.net.
FC500IP - IP Module
The FC500IP is an IP Module which is used to connect
control units in the FC500 range to a LAN.
The IP Module may be connected to a LAN using a pri
-
vate IP address or a DHCP address.
The same procedures may be performed using the Fi
-
reClass500 console application, either through the
serial port or the network. With a public IP address, it is
also possible to manage and monitor the control unit
form anywhere in the world, as long as you have access
to the Internet.
FC500PSTN - Telecom Module
FC500PSTN is a Telecom Module which allows implemen-
ting the functions of Channel Telephone Dialler and Telemo-
nitoring (functions E and J of standard EN54-1:1996), within
the control panels of the FC500 series.
General features:
Ø
Possibility of associating up to 3 voice messages for
each event.
Ø
Built-in multiprotocol digital communicator.
Ø
32 programmable telephone numbers.
Ø
Programming by PC.
Ø
Check for telephone line cutting.
Ø
Excluded line tone check.
Ø
Overvoltage protection.
Ø
Digital message recording playback.
Ø
Built-in speaker for message playback.
4B - Universal Base
The 4B Universal base is for use with the
FC460/FC400/600 series of detectors.
The base may be fixed directly to:
Ø
British (fixing centres 50mm) or European (fixing
centres 70mm) conduit box;
Ø
Euro Mounting Box AB-EM;
Ø
suspended ceiling, via the CTA adapter;
Ø
Directly to the ceiling.
FC400H or FC460H - Addressable Heat Detector
The FC400H heat detector forms part of the FC400 Se
-
ries of Addressable Fire detectors.The detector is inten
-
ded to plug into the following:
Ø
5B 5”Universal Base
Ø
FC450IB 5” Isolator Base
Ø
FC430SB Low Power Sounder Base
Software within the controller is used to interpret the re
-
turned heat values to raise an alarm or other appropria
-
te response according to the type of detector configured
in Fire Class 500 Console.
The mode of detector may be:
Ø
EN54-5 A1R, rate-of-rise normal ambient
Ø
EN54-5 A2S, fixed 60
o
C
Ø
EN54-5 CR, rate-of-rise high ambient.
FC400P or FC460P - Addressable Optical
Smoke
The FC400P optical smoke detector forms part of the
FC400 Series Addressable Fire detectors.
Ø
FC450IB Isolator Base
Ø
5B 5” Universal Base
Software within the controller is used to interpret the re-
turned optical and heat values to raise alarm or other
appropriate response according to the type of detector
configured in Fire Class 500 Console.
FC400PH or FC460PH - Addressable
Optical Smoke & Heat Detector
The FC400PH optical smoke and heat detector forms
part of the FC400 Series of Addressable Fire detec
-
tors.The detector is intended to plug into one of the fol
-
lowing:
Ø
5B 5” Universal Base
Ø
FC450IB 5” Isolator Base
Software within the controller is used to interpret the re
-
turned optical and heat values to raise alarm or other
appropriate response according to the type of detector
configured in Fire Class 500 Console. The mode of de
-
tector may be:
Ø
Mode 1 - Optical smoke only detector (sensitivity
High, Normal or Low)
Ø
Mode 2 - Optical ( sensitivity High, Normal or Low )
and heat fixed temperature 60
o
C (A2S)
Ø
Mode 3 - Heat only rate-of-rise (A1R) detector (no
sensitivity selection)
Ø
Mode 4 - Heat fixed temperature 60
o
C (A2S) (no sen
-
sitivity selection)
54 Addressable Fire Control Panels FC500