IP interface
For an explanation of the various commands and pro
-
gramming procedures, please refer to the dedicated
FC500IP interface manual.
CLOCK
The Date/Time option from the CLOCK menu is for the
control panel clock settings.
Enter the required Time and Date.
In case schedule the automatic application of summer
time if required.
LOG
This option allows to read the Log stores events.
When a Customer will be closed, the system save auto
-
matically the present LOG. In this way the LOG is al
-
ways updated. Description of the icons in the LOG bar:
Up load from Board: click-on this icon to upload the
LOG of the connected control panel.
Export LOG to file: click-on this icon to export the
LOG in a .fcl file.
Import LOG from file: click-on this icon to import
the LOG from a .fcl file.
Apply filter: click-on this icon to select the LOG fil-
ter (if necessary):
Ø No filter
Ø Restore
Ø
Alarm
Ø
Prealarm
Ø
Warning
Ø
Fault
Ø
Generic
Ø
Walk test
Print a text file; in this case the control panel Event
Log, or part of it.
Filter: click-on this icon to select others LOG filter (if
necessary):
Ø
Filter by panel
Ø
Filter by Loop
Ø
Filter by device
Ø
Filter by zone.
The following data will be stored in the LOG: the Event's
Number, the Date, the Time, the Class (Fault, Alarm,
Warning, Generic and Walk test), the Event's descrip
-
tion, the Control panel number, the Loop, the Device
type, the Status, the Threshold and the Zone.
Clicking on the icon will delete the Event Log, or
part of it.
Battery Calculation
The Battery calculation window allows you to see (Figu
-
re 31):
Ø
the FireClass500 Loads
Ø
the Loop1,Loop 2 devices loads
in the condition of Normal Load and Alarm Loads
(percentage of devices in alarm status), when the Ma
-
ins faults.
Below this window, in the option "Others Load", if nee
-
ded, the Loads on Auxliary terminals will be inserted.
Automatically the Total Load and the Battery needed
will be shown.
Fixed the Stand-by hours, Alarm minutes and Alarm
percentage values the calculation will be done.
Battery calculation Parameters:
Ø
Stand-by hours (From 1 to 144 h)
Ø
Alarm minutes (From 1 to 240 h)
Ø
Alarm percentage
Battery Type: this is the battery (Ah) arising from calcu
-
lation.
Battery calculation constraints:
Ø
Lock stand-by hours
Ø
Lock battery type.
Lock stand-by hours: "Battery Type" value (Ah) will be
calculate, fixed Stand-by hours, Alarm minutes and
Alarm percentage ;
Lock battery type: "Stand-by hours" value will be cal-
culate, fixed Battery Type (Ah), Alarm minutes and
Alarm percentage.
+
The software calculation is a rough calcolation and
cannot substitute the Installer and/or Qualified per-
son calculation.
Loop Wiring calculation
In the same Battery Calculation window (see Figure
31), on the right, FireClass500 Console allows you the
Loop Wiring Calculation.
After the Loop devices have been programmed, clicking
on Loop1 or Loop 2 field (Installation Loop), the Loop
Wiring Calculation window will open. Insert the wire
type in the Max wire Resistance field (value in
Ohm/Km); automatically, the max Loop length will be
shown in the Loop Length field (value in m.) .
Vice versa, inserted the Loop Length, automatically,
the Max wire Resistance (Wire type) will be shown.
Clicking on this Icon the Wire database will be
open. In this database it is possible to insert many type
of wires and so these type of wires will be used in the
Loop wire calculation.
PC PROGRAMMING 37