FC410QIO Quad input output module
The module provides four monitored digital inputs and
four potential free relay changeover outputs.
The outputs are monitored with parallel contacts of the
relays. The outputs can be connected to an Auxiliary
Voltage source and its voltage can be monitored.
Additionally, all the outputs can be connected to the
HVR800, for switching high power galvanic isolated loads.
For more details refer to the HVR800 documentation.
The module has an integral loop isolator. If this activa
-
tes a yellow LED illuminates. The activation remains in
place until the short is removed.
The digital input monitoring and isolator functions are
both configurable.
Maximum relay current: 2A.
Maximum relay voltage: 30V.
FC410QRM Quad relay module
The module provides four potential free relay changeo
-
ver outputs. The outputs are monitored, with parallel
contacts of the relays. The outputs can be connected to
an Auxiliary Voltage source and its voltage can be mo
-
nitored.
Additionally, all the outputs are configurable to the HVR
(High Voltage Relay) mode, which allows you to con
-
nect up to four HVR800 modules for switching; for
example 240V loads galvanically isolated.
The module has an integral loop isolator. If this activa-
tes a yellow LED illuminates. The activation remains in
place until the short is removed.
Maximum relay current: 2A.
Maximum relay voltage: 30V.
FC410LPBS-R/W loop powered sounders
and sounder-beacons (EN54-23)
The FC410LPBS Series of Loop Powered Addressable
Sounder/ Sounder-Beacons are designed to be driven
from a FC501 control panel via the addressable loop.
The FC410LPBS Series of sounders/sounder beacons
consist:
FC410LPBS-R: Sounder (indoor use) - red housing
FC410LPBS-W: Sounder (indoor use) - white housing
FC410LPAV: Sounder-Beacon IP65 (outdoor use) - red
housing
The sounder has two volume settings ‘High’ (103 dB ±3)
or ‘Low’ (90 dB ±3).
The beacon has two flash rates ‘Slow Flash’ (1/2 Hz) or
‘Fast Flash’ (1 Hz).
The FC410LPBS devices are synchronised, but not
synchronous with other FireClass sounders and beacons
of the FC400 serie.
The first flash of the beacon is synchronised with the start
of the tone.
The FC410LPBS devices have a built in two port isolator.
FC430LPBSB Loop Powered Addressable
Sounder/Beacon Base (EN54-23)
The FC430LPBS Series of Loop Powered Addressable
Sounder/Sounder- Beacons are designed to be driven
from an FC501 control panel via the addressable loop.
Tone, volume and flash rates are set in FireClass Console.
The sounder has four volume settings ‘High’ (90dB ±3),
‘Mid High’ (80 ±3dB), ‘Mid Low’ (70 ±3dB)or ‘Low’ (60dB
±3). The beacon has two flash rates ‘Slow Flash’
(1/2Hz) or ‘Fast Flash’ (1Hz).
The FC430LPBS Series have a built-in line isolator.
The table below, cross connect the managed devices in
the current version and the new EN54-23.
+
It is possible to substitute old devices with corre-
spondent new ones (EN54-23), keeping the same
program data. When the old device is physically re-
moved from the loop, the control panel will signal
the "No answer" fault. When the new device with
the same address is connected to the loop, the
control panel will restore the "No answer" fault and
automatically update its internal database with the
new device type.
It is not possible to substitute new devices
(EN54-23) with old ones (they are not EN54-23 ap
-
proved).
58 Addressable Fire Control Panels FC500
FireClass Product
code (Current Dev.)
FireClass Device
name (Current Dev.)
Description
FireClass
Product code
(EN54-23 Dev.)
FireClass
Device name
(EN54-23 Dev.)
516.800.758 FC430LPASB
Loop Powered Beacon
Sounder Base
516.800.973 FC430LPBSB
516.800.763 FC410LPAVR
Loop Powered
Beacon/Sounder (indoor use)
red
516.800.970
FC410LPBS-R
516.800.764 FC410LPAVW
Loop Powered
Beacon/Sounder (indoor use)
white
516.800.971 FC410LPBS-W
516.800.766 FC410LPAV
Loop Powered
Beacon/Sounder IP65
(outdoor use)
516.800.972
FC410LPBS