Mode 5 - Heat rate-of-rise (A1R) detector and optical
smoke (sensitivity High, Normal or Low)
Ø
Mode 6 - HPO (Advanced) smoke detector (sensivity
High, Normal or Low)
Ø
Mode 7 - HPO (Advanced) and heat fixed temperatu
-
re 60
o
C (A2S)
Ø
Mode 8 - HPO (Advanced) and heat rate-of-rise (A1R).
+
FC460P, FC460H and FC460PH, these devices
shall be managed only in backward compatible
mode, i.e. their new feature (auto-addressing) will
not be available . In the control panel and in the PC
software (FireClass500 console), they will be vi
-
sualized as the devices they substitute (FC400P,
FC400H and FC400PH respectively)
FC410LI - Line Isolator Module
The FC410LI Line Isolator Module is designed to be
used on the FC addressable controller loop circuits. It
monitors the line condition and when detecting a short
circuit will isolate the affected section whilst allowing the
rest of the addressing circuit to function normally.
The purpose of the FC410LI Line Isolator Module is to
ensure that, on a looped addressable system, no short
circuit fault can disable more detection devices than wo
-
uld be lost on a conventional non-addressable fire circuit.
FC410MIM - Mini Input Module
The FC410MIM Mini Input module is designed to moni-
tor fire contacts, such as extinguishing system control,
ventilation control, fire door control etc.The module pro-
vides one identifiable detection spur which is capable of
monitoring multiple normally open contacts or a single
normally closed contact.
The FC410MIM can be mounted in any electrical enclosu-
re with sufficient depth to accommodate FC410MIM and
the contacts monitored by the IN+ and IN- terminals, ie, no
field wiring. The remote LED (if required, not supplied)
must be located within the same electrical enclosure.
FC410MIO - Small Addressable Multi I/0
Module
The FC410MIO Multi I/O Module has three class B in
-
puts and two outputs from latching relays. The class B
inputs can monitor fire contacts such as extinguishing
system control, ventilation control, fire door control etc.
The two relays outputs are dry form C that provide
volt-free relay changeover contacts.
A maximum of two HVR800 High Voltage Relay Modu
-
les can be individually driven and controlled by an
FC410MIO if all HVR800s are powered by 24V dc or
24V ac. In this application, the HVR800s are controlled
by the two latching relays on the FC410MIO.
A maximum of four HVR800 High Voltage Relay Modu
-
les can be individually driven and controlled by an
FC410MIO if all HVR800s are powered by 120V ac or
240V ac. In this application, the HVR800s are control
-
led by the four control outputs (O1+/O1- to O4+/O4-) on
the FC410MIO.
FC410SIO - Single Input/Output Module
The FC410SIO Single Input/Output Module is designed
to provide a monitored open collector input and a volt
free relay changeover output.
FC410SIO can switch up to2A@24Vdc.
FC420CP - Addressable Break Glass
Callpoint (indoor)
FC420CP Addressable Break Glass Callpoint is desi
-
gned to monitor and signal the condition of a switch
contact that is operated by activating the break glass
element. The type of alarm generated by the callpoint is
configured in FireClass 500 Console.The FC420CP call
point meets the requirements of EN54 Pt.11. The
FC420CP is fitted to a standard surface mount plastic
backbox, standard single gang metal plaster box (35
mm for flush mounting) or standard single gang metal
plaster box (25 mm) with backbox.
FC421CP - Addressable Break Glass
Callpoint (outdoor)
FC421CP Weatherproof Addressable Break Glass Cal
-
lpoint is designed to monitor and signal the condition of
a switch contact that is operated by activating the break
glass element. The type of alarm generated by the cal
-
lpoint is configured in FireClass 500 Console. The
FC421CP callpoint meets the requirements of EN54
Pt.11. The FC421CP is fitted into a standard weather-
proof break glass callpoint housing.
FC430SAB/SAM - Sounder Base Address
Modules
The Sounder Base Address Modules (FC430SAM
/FC430SAB) are designed to control a loop powered soun-
der base for use with the FCsystem, one variant
(FC430SAB) has an integral beacon. They may also be
used to drive a relay base. The units are used to supply the
address decoding in place of a detector, thus providing a
loop powered sounder when used in conjunction with an
FC430SB. The modules are colour matched to the soun
-
der bases. The FC430SAM/FC430SAB is locked into the
base using the locking device integral to the sounder base.
FC430SB - Loop Low Power Sounder Base
The FC430SB Loop Low Power Sounder Base provides
an additional sounder function on the FC addressable
loop circuit. The FC430SB Loop Low Sounder Base re
-
quires an associated detector or a FC430SAB module
or a FC430SAM module in order to operate, as it uses
the address of the detector or module that is fitted to it.
Removal of the detector or module or loss of power to the
loop will cause the sounder to cease operating. If a de
-
tector is associated to FC430SB, the FC430SB is acti
-
vated only when the detector (i.e. the detector which is
mounted on it) enters the alarm condition (according to
its settings). It is not silenceable.A maximum of 45 So
-
under Bases at full volume may be connected to the
loop.
ACCESSORY 55