INSTALLATION
!
Installation of this system must be carried out
strictly in accordance with the instructions in
this section, and in compliance with the local
safety regulations in force.
To install the control panel work through the following
steps:
Ø
Choose suitable mounting locations for the Control
panel, detectors, fire warning and fire control devi
-
ces.
Ø
Lay the cables between the Control panel and the
system peripherals.
Ø
If necessary, install any accessory modules.
Ø
Before mounting the Control panel to the wall, insert
the LED and Keys Labels (supplied) in the Interface
User (see pag.17).
Ø
Carry out the necessary connections, leaving the po
-
wer-supply connection until last.
Ø Program the Control panel in accordance with the in-
structions in the “PROGRAMMING” section.
Ø Test the entire system (Control panel, detectors, fire
warning and fire control devices).
+
Accessory Modules should be installed before mo-
unting the Control panel to the wall.
Installing accessory boards
!
Ensure that the Control panel power supply
(Mains and Batteries) has been disconnected
before installing any accessory Modules.
Installing the Control panel
Work carefully through the following steps (see the Fi
-
gures 1, 2 and 3).
1. Remove the screws (2) and open the Control panel.
2. Drill the anchor screw holes.
!
Check for water pipes and electrical wiring be
-
fore drilling.
3. If necessary, using a hammer or similar tool, remo
-
ve the surface conduit wire knockouts 1.
+
The cable conduit union with the case must be se
-
cured by HB Flame Class (or higher) lock nuts.
4.
Pull the wires through the chased wire entry 21 then,
using the anchor screws, secure the backplate to the
wall.
Installing FC500REP Repeaters
Repeaters can be wall mounted, or flush mounted to an
ave
®
BL08 outlet box (or similar).
Work carefully through the following steps.
1. Lay the connection cables (refer to “Connecting
Repeaters”).
2. Remove the screws 2 (see Figure 3) and open the
Repeater FC500REP.
3. If you are flush mounting the Repeater, go to step
5. If you are wall mounting the Repeater, drill the
anchor screw holes 12.
4. Pull the wires through the wire entry 21, then, using
the anchor screws, secure the Repeater to the wall.
5. Complete the connections to the terminal board 23
of the RS485 Interface, as described in the “Con-
necting Repeaters” section.
- Connect the earth wire to the threaded support 7a
on the cover, as illustrated in Figure 3.
6. Set the Repeater Address.
Installing the FC500PS e FC500IP board
Please refer to the dedicated manuals.
Installing the FC500 Slave control panel
See "Installing the Control panel paragraph".
INSTALLATION 19