QUICK START-UP PROCEDURE
These procedure allows the quick start-up of the
FC510/520 fire detection system.
When the loops are wired, electrically verified and all
the devices have been programmed with their related
address (using the special FC490ST Loop Service Tool)
and installed to the loop, it is possible to connect the lo
-
ops terminals to the panel.
+
Before powering-on the Fire control panel, ensure
that the Earth Line has been connected.
!
Be sure that the main voltage is the same of the
input voltage set on the BAQ140T24 power
supplier. Move the switch 35a if the BAQ140T24
input voltage is different from the main voltage,
ONLY when the power supplier is not connec
-
ted to the main power. Please note that the po-
wer supplier will be damaged if it is connected
to the 230 V main power when it is set for 110 V.
PROCEDURE
1. Power-on the panel
2. Insert the data and time , if requested ( this step it is
important to guarantee the Log file consistency).
At this point the panel will start the first system initializa
-
tion verifying the loops integrity, warming up the smoke
sensor circuitry, looking for not address programmed
devices over the loops and searching devices with the
same address.
+
NOTE: The panel in this phase is configured to ma
-
nage closed loops (4 wires loop), if it is connected
to a spur (2 wires loop) will be generate broken
loop faults.
At the end of this first initialization phase will be activa
-
ted on the user interface the main page with the capabi
-
lity to accede to the command and control functions
3. Select the function Program pressing the key F1
4. Insert the installer password (default=00000) every
digit will be masked by * symbol.
5. Choose the option Auto pressing the key 1
The panel will start the enrolling procedure. At the end
of this phase will be presented the result of the enrolling
in terms of loop with devices connected (OK) or not
(KO) and it will be possible view the details for each acti
-
ve loop (number of detectors, number of modules, cur
-
rent drawn), pressing the key [ESC] it is possible to
reach again the main page.
+
If the enrolling result differ from the previously sto
-
red loop configuration a warning message will be di
-
splayed and it is possible to reject the present
enrolling result ,maintaining the previous configura
-
tion, or accept them.Suddenly after the enrolling
phase the panel starts the loops initialization phase.
At the end of this phase, which duration is related to the
number and type of the devices connected over the lo
-
ops, the panel it is able to act according the directive of
the EN54-2 standard.
+
The enrolling function will not be activated if there
are present loop related faults.
The functional parameters of the panel and devices at
the end of the enrolling procedure are listed below
n Detectors
FC400H: A2S mode
FC400P: standard mode, medium sensitivity
FC400PH: (temp. = A2S) + (Smoke = standard mode,
medium sensitivity).
FC400CH: (temp. = A2S) + (Carbon Monoxide = stan
-
dard mode, normal sensitivity).
+
All detectors activation will generate panel ALARM
n
Modules
FC410MIM: input style=C,NO
FC410SIO: input style=C,NO,
output NOT active
FC410MIO: inputs style=C,NO,
outputs NOT active
FC420CP: Call-point fully active
FC430SAB: NOT active