EasyManua.ls Logo

FireClass 500 - Parameters Detectors Programming

FireClass 500
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Ø
New device from clipboard: allow you to copy
the devices data from a customer and after paste
them in another customer.
Ø Upload from board: to download the program-
ming (via serial link) to the connected control panel.
Ø Download to board: to upload all the program-
ming (via serial link) of the connected control panel.
Ø Print a text file; in this case, the list of devices fit-
ted within the control panel loop.
Ø Device's details: a further window allow you to see the
points and the Outputs where the devices is enabled.
Ø
Select: allow you to select all present devices.
+
If different devices have common programming pa
-
rameters, you can use the multiple selection of the
devices and assign the same parameters.
+
You can see (view) the list of devices included
in List or Grid, put the check.
Select devices
Click-on Panel 1, select Loop 1
or Loop 2, click on "new device" , the window
in Figure 26 will shown:
select the programming devices, enter a valid ad
-
dress, and after click-on
3 OK to put the devices
in configuration. For others devices, repeat the
same procedure.
Remove devices Select the device, therefore
click-on "Remove device" , and confirm the
choose
3 OK.
Loop Loading At the end of "Device programming
window", Figure 26, there is a Loop Loading section.
Here, the "Loop drain" and the "Signal drain" will be
shown . On the right, the "Loop drain in stand by", the
"Loop drain in alarm (50%)", and the "battery needed"
will be shown.
+
The remote LEDs may be entered in the calculation
The percentage shown in the "Loop drain in alarm
(50%)" is the programmed value in "Battery calculation"
an option of Configuration menu (see dedicated para-
graph).
n
Parameters detectors programming
Click-on device in configuration, the relative program
-
ming window will shown (every device has the dedica
-
ted programming window).
For the detectors (see figure 26);
in the Multiple sources section:
32 Addressable Fire Control Panels FC500
Detector
Class
Typical application
Temperature
°C
Max. Application
Temperature
°C
Min.Static
Response
Temperature
°C
Max.Static
Response
Temperature
°C
A1 25 50 54 65
A2 25 50 54 70
B 40656985
C 558084100
D 709599115
E 85 110 114 130
F 100 125 129 145
G 115 140 144 160
Table 6 Detector classification Temperature - Detector shall conform to one or more of the following classes: A1,
A2, B, C, D, E, F o G . Manufacturers may optionally give additional information concerning the type of response exhi
-
bited by the detector, by adding the suffix S or R to the above classes.
Detectors, with a suffix S to their class, do not respond below the minimun static response temperature, even at high
rates of rise of air temperature.
Detectors, with a suffix R to their class, incorporate a rate of rise characteristic, which meets the response time requi
-
rements for high rates of rise of air temperature even when starting at air temperature substantially below the typical
application temperature (EN54-5:2000).
Figure 27 Detector Disablement confirmation window.

Table of Contents

Related product manuals