149
DEVICEINDEX;NumDevice_1
Protocol_1;leDenitionName_1
...
...
DEVICEINDEX;NumDevice_N
Protocol_N;leDenitionName_N
Colour code:
Black: xed text.
Blue: device-specic information or data.
Where:
NumDevice_N: the device “index” in the connection interface conguration le for device N
(see section 3.1.2.2.2: “Denition le content”).
leDenitionName_N: denition le name for device N.
4.1.3.2 Data
Data formatting is identical regardless of the device or interface.
The reported values are raw and must be linked to the conguration on the device or the interface in its
denition le. The IS must interpret the data using the raw data le and the denition le to be able to
apply factors A and B and the unit for each variable. (see section 3.1.2.2.2: “Denition le content”)
The “action” eld value for the device or the interface dened in its denition le is used for the following
action:
“ACTION” CODE DESCRIPTION
0 No values are reported.
1 The parameter value is reported.
2 The min, max and mean values are reported.
4 The instant value is reported.
8 The instant value is reported and and alarm is generated every time the
value changes.