• <idTable>_<variableName>: for each variable in the table declared in the SunSpec
standards, a corresponding variable will be associated with the device. The variable
name will consist of the table identier, followed by the variable name
• <idTable>_<repeatBlock>_<variableName>: in the case of variables that come from a
repeating block, the variables are created using the table identier, the repetition number,
as well as the name of the variable, so that the generated name is unique.
The variables generated are, by default, of the “Parameter” type and will therefore have the
“Action” code 1, with the exception of the variables of tables 101, 102, 103, 111, 112, 113,
123, 160 and 401 which will be created with the “Immediate” type, i.e. code 4.
It should also be noted that the following variables will have a tag automatically applied:
• WMaxLimPct of table 123 receives the tag “cmdPwrPercent”
• WMaxLimPct_RmpTms of table 123 receives the tag “WMaxLimPct_RmpTms”
• WMaxLimPct_Ena of table 123 receives the tag “WMaxLimPct_Ena”
• VarPct_Mod of table 123 receives the tag “VArPct_Mod”
Note that if the device already existed in the conguration and the user forces a new import,
the previous device is not overwritten. A new device is created in addition to the pre-existing
device.
If the user clicks on the “Cancel” button, this list is erased, and the page displays the detection
type selection screen again.
3.2.1.1.2 Detection of Proprietary Protocol Equipment
(see proprietary protocol application note)
3.2.1.2 Manual Device Management
Devices can be managed manually on the web site.
Everything is managed from the “Devices” tab described previously (see section 3.2.1: “Devices”).
3.2.1.2.1 Add a Device
To add a device, rst click the “+” button: