contact@webdyn.com | webdyn.com
V2.05 subject to changes | Webdyn © by Flexitron Group
Baudrate baudrate Serial connection speed in bauds:
•1200
•2400
•4800
•9600
•19200
•38400
•57600
•115200
•230400
•460800
Data bits data_bits Number of data bits:
•7
•8
Parity parity Serial connection parity:
•None: no parity
•Odd: odd parity
•Even: even parity
Stop bits stop_bits Number of stop bits:
•1
•2
InterFrame interframe The waiting time between 2 frames exchanged on the
serial port. This time is expressed in ms.
See the explanation in section “3.1.2.1.3.3 - Serial port
conguration”.
Forwarded
TCP port
forwarded_port Forwarded TCP port.
If there is a value in this eld, the concentrator opens a
modbusTCP port on the entered port number.
When modbusTCP devices connect to this port, all sent
requests are directly forwarded to the modbusRTU bus
and the response is returned to the connected device
using this modbusTCP port.
This option is used to create a communication tunnel
between modbusTCP devices and the local modbusRTU
network.
The requests are slotted between the concentrator’s
internal monitoring requests.