Safety Inspections
Safety inspection This section outlines the safety inspection for the device described in this service manual.
It has been structured in compliance with "DIN VDE 0701-0702” and "ÖVE/ÖNORM
E8701-1”.
Please also be aware of the requirements and standards relevant to your country, as the
measured values or steps taken during the tests may vary.
Should there be no relevant requirements and standards in your country, Fronius recom-
mends that this test should still be carried out.
The safety inspection must only be carried out on a fully assembled device.
Responsibility The repair engineer is responsible for carrying out and documenting the safety inspection
properly and for making the correct decision regarding the outcome of the inspection. Fro-
nius accepts no liability in this respect.
Should any defects be identified during the test, then the entire safety inspection must be
repeated once such defects have been rectified.
The following tests must be performed in the prescribed sequence. Each test must be
passed before the next test is started. If it is not possible to perform a particular test, the
examiner must decide whether the safety of the device can nevertheless still be verified.
The examiner bears full responsibility and liability for this decision. Justifications for the re-
sulting decision must be documented in the test record under "Comments".
Area of applica-
tion
A safety inspection must be performed after any repair, maintenance or modification work,
or if stipulated by applicable national standards.
Inspection staff
qualifications
The safety inspection may only be performed by an appropriately qualified electrician.
These are persons who due to their specialist training, knowledge and experience of the
relevant regulations are able to evaluate the tasks they are assigned as well as to identify
and avoid electrical and other possible hazards.
Measuring instru-
ments
The following requirements concerning measuring equipment as defined by DIN VDE
0701-0702 and ÖVE/ÖNORM E8701-1 must be observed. Also refer to the applicable re-
quirements and standards in your country:
Ground conductor resistance
- The measuring voltage may be a direct or alternating voltage
- The open circuit voltage must remain within a range of 4 V to 24 V
- The measuring current within the measuring range of 0.2 to 1.99 must not drop
below 0.2 A

Table of Contents

Other manuals for Fronius Primo 3.0-1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius Primo 3.0-1 and is the answer not in the manual?

Fronius Primo 3.0-1 Specifications

General IconGeneral
PurposeSolar panel
Efficiency98 %
Output power3000 W
Input current12 A
Input voltage80 - 1000 V
Output voltage- V
Input frequency50 - 60 Hz
Power supply typeAuto
Adjustable output voltage-
International Protection (IP) codeIP65
Product colorBlack, Grey
Built-in displayYes
Operating temperature (T-T)-40 - 55 °C
Weight and Dimensions IconWeight and Dimensions
Depth204 mm
Width431 mm
Height645 mm
Weight21500 g

Related product manuals