406 Faulty temperature sensor 
in DC semiconductor mod-
ule
1. Faulty temperature sensor in 
semiconductor module
1. Replace DC PC board
2. Faulty power stage set cir-
cuit
2. Replace DC PC board
407 Faulty temperature sensor 
on power stage set
1. Faulty temperature sensor 
on power stage set
1. Replace AC PC board
2. Faulty power stage set cir-
cuit
2. Replace AC PC board
408 Unacceptably high DC 
braking detected on the in-
verter
1. Asynchronous AC grid 1. Check AC grid
2. Faulty power stage set 2. Replace AC PC board
412 Set fixed voltage is outside 
the permitted MPP range
1. Fixed voltage has been set 
too high or too low
1. Check adjustments in Ser-
vice menu
415 Enable signal: option cards 
activated
1. Option card does not output 
an enable signal for feeding 
energy into the grid
1. Automatic correction, option 
card has stopped the inverter
416 - 425 No communication possible 
between power stage set 
and Recerbo
1. Occurs once - PSP commu-
nication fault
1. Automatic correction
2. Unknown option card block-
ing the inverter
2. Software update
3. Check ribbon cable between 
filter PC board and power 
stage set
3. Replace ribbon cable
4. Faulty Recerbo 4. Replace Recerbo
5. Faulty filter PC board 5. Replace filter PC board
6. Faulty power stage set 6. Replace AC PC board
426 Intermediate circuit charg-
ing takes too long
1. DC voltage too weak 1. Restart inverter or check wir-
ing
2. DC choke does not contact 
cleanly
2. Check DC choke wiring
3. Faulty DC booster 3. Replace DC PC board; re-
place AC PC board if neces-
sary
427 Power stage set not ready 
for too long (timeout)
1. Software fault 1. Software update
2. Measurement fault on power 
stage set
2. Replace AC PC board
431 Power stage set is in boot 
mode
1. Power stage set is being au-
tomatically programmed
1. Automatic correction
2. Power stage set cannot be 
automatically programmed
2. Software update
3. Faulty filter PC board 3. Replace filter PC board
4. Faulty Recerbo 4. Replace Recerbo
5. Faulty power stage set 5. Replace AC PC board
432 Permanent fault in power 
stage set management
1. Power stage set could not 
communicate with Recerbo
1. Restart inverter or perform 
software update
2. Faulty power stage set 2. Replace AC PC board
3. Faulty Recerbo 3. Replace Recerbo
Code Description Behaviour Remedy