DC input data
Feed-in start-up input voltage in grid
operation
5)
80 V
Max. input current
PV 1
PV 2
12.5 A
12.5 A
Max. short circuit current of module
array (I
SC PV
)
PV 1
PV 2
20 A
20 A
Max. total short circuit current of
module array
(I
SC PV1
+ I
SC PV2
= I
SC max
) 40 A
Max. inverter backfeed current to the
array
3)
PV 1
PV 2
20 A
20 A
Number of inputs - PV 1 2
Number of inputs - PV 2 1
Max. capacity of the module array
against earth
1000 nF
Insulation resistance test limit value
between module array and earth (on
delivery)
8)
100 kΩ
Adjustable range of insulation resist-
ance test between module array and
earth
7)
10 - 10,000 kΩ
Limit value and tripping time of the
sudden residual current monitoring
(on delivery)
30 / 300 mA / ms
60 / 150 mA / ms
90 / 40 mA / ms
Limit value and tripping time of the
continuous residual current monitor-
ing (on delivery)
300 / 300 mA / ms
Adjustable range of continuous resid-
ual current monitoring
7)
30 - 300 mA
Cyclic repetition of the insulation res-
istance test (on delivery)
24 h
Adjustable range for the cyclic repeti-
tion of the insulation resistance test
-
DC input data battery
Max. voltage
9)
531 V
Min. voltage 160 V
Max. current 12.5 A
Max. output 5210 W
DC inputs 1