Demand Re-
sponse Modes
(DRM)
Here you can enter a value for the apparent power input and the apparent power
output for the Australia country setup.
Inverter "Enforce Standby"
When the function is activated, the feed-in mode of the inverter is interrupted.
This enables a powerless shutdown of the inverter and protects its components.
When the inverter is restarted, the standby function is automatically deactivated.
"PV 1" and "PV 2"
Parameter Value range Description
"Mode" Off The MPP tracker is deactivated.
Auto The inverter uses the voltage at which the
max. possible power of the MPP tracker is
possible.
Fix The MPP tracker uses the voltage defined
in the "UDC fix".
"UDC fix" 80 ‑ 530 V The inverter uses the fixed preset voltage
used at the MPP tracker.
"Dynamic Peak
Manager"
Off The function is deactivated.
On The entire solar module string is checked
for optimisation potential and determines
the best possible voltage for feed-in mode.
"Ripple Control"
Ripple control signals are signals sent out by the energy company to switch con-
trollable loads on and off. Depending on the installation situation, ripple control
signals may be attenuated or amplified by the inverter. The settings below can be
used to counteract this if necessary.
Parameter Value range Description
"Reduction of
Influence"
Off The function is deactivated.
On The function is activated.
"Frequency of
Ripple Control
Signal"
100 ‑ 3000 Hz The frequency specified by the energy
company must be entered here.
"Grid Induct-
ance"
0.00001 ‑ 0.00
5 H
The value measured at the feed-in point
must be entered here.