Select the breaker based on MCA of the table above. ●
Select the wire diameter based on the larger value of MCA or TOCA of the table above and select ●
a wire diameter which withstands the breaker capacity.
*1 Wiring Spec : These values are recommended data. Please select the wiring spec in accordance with the regional cable
standard.
*2 Limited Wiring Length : This wiring length is in case voltage drop less than 2%. When wiring length extend longer,
select the wiring size of larger diameter.
RLA : Rated Load Amp of compressor under the standard condition.
MCA : Min Circuit Amp = Max Operating Current (Full Load)
MSC : Max Starting Current
TOCA : Total Value of Each Over Current Set
MFA : Main Fuse (Circuit Breaker) Current
ELECTRIC CHARACTERISTICS8.
Rated Value Electric Characteristics
Power Supply Full Load Characteristics Wiring Specications *1 Compressor
Outdoor Fan
Motor
HP Model name Hz
Voltage
(V)
MCA
(A)
TOCA
(A)
MSC
(A)
MFA
(A)
Power
Cable
(mm
2
)
Earth
Cable
(mm
2
)
Limited
Wiring
Length
(m) *2
RLA
(A)
Output
(W)
FLA
(A)
4 AJ
A40LALH 50 230 30.3 29.5 29.5 32 6 4 18 24 100 0.66
5 AJ
A45LALH 50 230 30.3 29.5 29.5 32 6 4 18 24 100 0.66
6 AJ
A54LALH 50 230 30.3 29.5 29.5 32 6 4 18 24 100 0.66