Note : Specications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
CASSETTE TYPE2-2.
Model name AUXD18GALH AUXD24GALH
Power source 230V ~, 50Hz
Available voltage range 198 to 264 V
Capacity
Cooling
kW
5.6 7.1
Heating 6.3 8.0
Input power W 39 46
Fan
Airow rate
High
m
3
/ h
(l / s)
1,150
(319)
1,280
(356)
Med
940
(261)
1,040
(289)
Low
870
(242)
870
(242)
Type x Quantity Turbo × 1
Motor output W 80
Sound
pressure
level
High
dB(A)
36 38
Med 30 33
Low 29 29
Heat
exchanger
Length
mm
2,054
Fin pitch 1.20
Rows x Stages 2× 10
Face Area m
2
0.42
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit(Aluminium)
Surface treatment Hydrophilic coating
Air lter
Type Anti-mold
Net material PP honeycomb
Enclosure
Material galvanized sheet iron
Colour -
Dimensions
(H x W x D)
Net Main body
mm
246 × 840 × 840
Gross 318 × 960 × 980
Weight
Net
kg
22
Gross 27
Connection
pipe
diameter
Liquid (Flare)
mm
ø 9.52
Gas (Flare) ø 15.88
Drain hose VP25 [ø 25(I.D.) ; ø 32(O.D.)]
Cassette
grille
Model name UTG-UGYA-W(FUJITSU brand); UTG-UGGA-W(GENERAL brand)
Colour
WHITE
Approximate colour of MUNSELL N9.25/
Dimensions
(H x W x D)
Net
mm
50 × 950 × 950
Gross 115 × 1,020 × 1,000
Weight
Net
kg
5.5
Gross 8.5
- (04 - 13) -
INDOOR
UNITS
INDOOR
UNITS