CAPACITY COMPENSATION COEFFICIENT6.
COMPENSATION COEFFICIENT OF PIPE LENGTH
The tables give the compensation coefcient of pipe length owing to installation position (pipe
length, height difference). Pipe length and height difference are the length and the height
difference between outdoor unit and indoor unit.
Cooling
z
Pipe length (m)
5 7. 5 20 30 40
50 60 70 80 90 100 110 120
Height
difference
H
(m)
outdoor
unit is
upper than
Indoor
unit.
30 - - - 0.942 0.921 0.899 0.877 0.855 0.833 0.812 0.790 0.768 0.746
20 - - 0.969 0.947 0.925 0.903 0.881 0.860 0.838 0.816 0.794 0.772 0.750
7.5 - 0.998 0.972 0.950 0.928 0.906 0.884 0.862 0.840 0.818 0.796 0.774 0.752
5 0.999 0.999 0.973 0.951 0.929 0.907 0.885 0.863 0.841 0.819 0.797 0.775 0.753
0 1.000 1.000 0.974 0.952 0.930 0.908 0.886 0.864 0.842 0.820 0.798 0.776 0.754
outdoor
unit is
under than
Indoor unit
-5 1.000 1.000 0.974 0.952 0.930 0.908 0.886 0.864 0.842 0.820 0.798 0.776 0.754
-7. 5 - 1.000 0.974 0.952 0.930 0.908 0.886 0.864 0.842 0.820 0.798 0.776 0.754
-20 - - 0.974 0.952 0.930 0.908 0.886 0.864 0.842 0.820 0.798 0.776 0.754
-30 - - - 0.952 0.930 0.908 0.886 0.864 0.842 0.820 0.798 0.776 0.754
Heating
z
Pipe length (m)
5 7. 5 20 30 40
50 60 70 80 90 100 110 120
Height
difference
H
(m)
outdoor
unit is
upper than
Indoor
unit.
30 - - - 0.994 0.991 0.989 0.987 0.984 0.981 0.978 0.975 0.972 0.970
20 - - 0.997 0.994 0.991 0.989 0.987 0.984 0.981 0.978 0.975 0.972 0.970
7.5 - 1.000 0.997 0.994 0.991 0.989 0.987 0.984 0.981 0.978 0.975 0.972 0.970
5 1.000 1.000 0.997 0.994 0.991 0.989 0.987 0.984 0.981 0.978 0.975 0.972 0.970
0 1.000 1.000 0.997 0.994 0.991 0.989 0.987 0.984 0.981 0.978 0.975 0.972 0.970
outdoor
unit is
under than
Indoor unit
-5 1.000 1.000 0.997 0.994 0.991 0.989 0.987 0.984 0.981 0.978 0.975 0.972 0.970
-7. 5 - 1.000 0.997 0.994 0.991 0.989 0.987 0.984 0.981 0.978 0.975 0.972 0.970
-20 - - 0.997 0.994 0.991 0.989 0.987 0.984 0.981 0.978 0.975 0.972 0.970
-30 - - - 0.994 0.991 0.989 0.987 0.984 0.981 0.978 0.975 0.972 0.970
COMPENSATION COEFFICIENT OF FROSTING / DEFROSTING
(HEATING OPERATION)
To take the effects of accumulated frost and defrosting operation on heating capacity into
consideration, the capacity of outdoor unit should be corrected by compensation coefcient
shown in the table below.
Outdoor temperature
(°CDB / °CWB)
-15 / -16 -9 / -10 -7 / -8 -5 / -6 -3 / -4 0 / -1 2 / 1 5 / 4 7 / 6
Compensation coefcient 0.96 0.94 0.91 0.88 0.85 0.83 0.85 0.90 1.00