RB UNIT5.
SPECIFICATIONS5-1.
Model name UTP-RX01AH UTP-RX01BH UTP-RX01CH UTP-RX04BH
Power source 1 Phase 230V ~ 50Hz
Available voltage range 198 to 264V
Number of branches 1 1 1 4
Maximum number of connectable indoor units per
branch
3 8 8 8
Maximum capacity of connectable indoor
units(Q)
kW
Q ≤ 8.0 Q ≤ 18.0 Q ≤ 28.0 Q ≤ 56.0 *1
Maximum capacity of connectable indoor
units per branch(Q)
Q ≤ 8.0 Q ≤ 18.0 Q ≤ 28.0 Q ≤ 18.0
Input power W 17 24 31 96
Running current A 0.11 0.16 0.22 0.64
Refrigerant type R410A
Dimensions
(H x W x D)
Net
mm
198×298×268 26658×428
Gross 262×833×374 3 48×1250×775
Weight
Net
kg
7 7. 5 8 31.5
Gross 9.5 10.5 11 39.5
Connection
pipe
Outdoor
unit side
Suction gas pipe
mm
ø12.70 ø19.05 ø22.22 ø28.58
Discharge gas pipe ø9.52 ø12.70 ø19.05 ø22.22
Liquid pipe None ø15.88
Indoor
unit side
Gas pipe ø12.70 ø19.05 ø22.22 ø19.05
Liquid pipe None ø9.52
Method Brazing
Operation range
°C -15 to 46
%RH 80 or less
*1: In case of two RB units connected in series ( total 8-branches ), maximum capacity of connectable indoor units
is up to 56.0kW.
- (10 - 31) -