SIGNAL AMPLIFIER AUTOMATIC ADDRESS SETTING1-5-1.
Caution
The Signal Amplifier Automatic Address Setting function can be used for a maximum of 40 ●
signal amplifiers installed within the same network.
Perform the automatic address setting of signal amplifiers on only one outdoor unit (master ●
unit) within the same network. (Do not set them again from other outdoor unit.)
When setting the address of a signal amplifier automatically, be sure to always set the ●
address on the printed circuit board of the Signal amplifier to “1”(factory setting).
Please perform automatic address setting after checking that filter mode setting of Signal ●
amplifier is completed.
1) After verifying that the system is normally, press the MODE/EXIT button (SW107) once.
LED105 LED104
LED105 LED104
2) Press the SELECT button (SW108) to display “F3” on the LED104.
(The display of the LED104 changes each time the SELECT button is pressed.)
LED105 LED104LED105 LED104 LED105 LED104 LED105 LED104
*1 *1
(Monitoring mode) (Setting mode) (Function mode)
(Error history mode)
*1 : The “F1” and “F9” modes are used for maintenance, so do not set them in regular
3) When “F3” appears on the LED104, press the ENTER button (SW109).
LED105 LED104
LED105 LED104
A ashing display appears on the LED105.
4) Press the SELECT button (SW108) to display “10” on the LED105.
LED105 LED104
LED105 LED104
5) When “10” appears on the LED105, hold down the ENTER button (SW109) for at least 3
seconds. (Unless it is held down for at least 3 seconds, the selection will not be conrmed.)
LED105 LED104
LED105 LED104
When the Automatic Address Setting function is activated, the display changes to “run.”
- (07-47) -
FUNCTION
SETTING