CONTROLLER CABLE WIRING4-4.
WIRING SPECIFICATIONS
Model type Connection to Wire Size Specication
System Controller USB Adaptor USB cable -
System Controller
Lite
USB Adaptor USB cable -
Touch Panel
Controller
Transmission line Refer to 6-4-3
Central Remote
Controller
Transmission line Refer to 6-4-3
Group Remote
Controller
Network Convertor
Remote controller
cable
0.33mm
2
Shielded, Polar 3core
Wired Remote
Controller
(UTY-RNR*) *2
Indoor unit
Remote controller
cable
0.33mm
2
to
1.25mm
2
Sheathed, Non-polar 2core,
Twisted pair *1
Wired Remote
Controller
(UTY-RLR*) *2
Indoor unit
Wired Remote
Controller
(UT Y-RNK*)
Indoor unit
0.33mm
2
Sheathed PVC cable Polar
3core *1
Simple Remote
Controller
Indoor unit
External Switch
Controller
Indoor unit
Remote controller
cable
0.33mm
2
Shielded, Polar 3core
External input 0.33mm
2
Shielded, Polar 2core,
Twisted pair
IR Receiver Unit
(UTB-*WC)
Indoor unit Connection cable - (5m cable attached)
IR Receiver Unit
(UT Y-LRH*B1)
Indoor unit Connection cable -
Remote Sensor Indoor unit Connection cable - (10m cable attached)
EV Kit Indoor unit Connection cable - (5m cable attached)
Drain Pump Unit Indoor unit Connection cable -
*1 : Use shielded cable (eld supplied) in accordance with the regional cable standard.
*2 : Refer to next page
Caution
Install in accordance with the regional standard. ●
Never bundle the power supply cable and controller cable together. Bundling these cords together ●
will cause misoperation.
Always ground for shilded cable both end. ●
For detail specification and connection, please refer to "Chapter 5 CONTROL SYSTEM". ●
Controller might be required to connect power supply cable and transmission line. Use separate ●
connection with other units for power suply cable.
- (06 - 58) -