EasyManua.ls Logo

Fujitsu Airstage J-II - Method of Capacity Calculation

Fujitsu Airstage J-II
836 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
METHOD OF CAPACITY CALCULATION3-2.
The capacity calculation method which takes the effects of air temperature, pipe length and
frosting/defrosting into consideration is shown below.
1. Calculate the estimated capacity of each indoor unit.
(1) Find
capacity of indoor unit at rated condition (TCin)r and at design temperature (TCin)d
[from 7. CAPACITY TABLE COOLING (INDOOR UNIT) or 8. CAPACITY TABLE HEATING (INDOOR UNIT)]
(2) Find the following compensation coefcient
[From 6. CAPACITY COMPENSATION COEFFICIENT].
Compensation coefcient of pipe length
Compensation coefcient of frosting/defrosting
(Heating calculation only
)
(3) Calculate
the estimated capacity of indoor unit (TCin)e.
COOLING:
Estimated capacity of indoor unit (TCin)e
= Capacity of indoor unit at design temperature (TCin)d
x Compensation coefcient of pipe length
HEATING:
Estimated capacity of indoor unit (TCin)e
= Capacity of indoor unit at design temperature (TCin)d
x Compensation coefcient of pipe length
x Compensation coefcient of frosting/defrosting
2. Calculate the compensated capacity of outdoor unit.
(4) Find
capacity of outdoor unit at rated condition (TCout)r
[From 2. MODEL LINE UP].
(5) Calculate
total rated capacity of indoor units : ∑(TCin)r
and
ratio to the rated capacity of outdoor unit : ∑(TCin)r / (TCout)r
.
(6) Find capacity of outdoor unit at design temperature (TCout)d
[using result of (5) and 4. CAPACITY TABLE (OUTDOOR UNIT)].
(7) Calculate the compensated capacity of outdoor unit (TCout)c.
COOLING:
Compensated capacity of outdoor unit (TCout)c
= Capacity of outdoor unit at design temperature (TCout)d
x Compensation coefcient of pipe length
HEATING:
Compensated capacity of outdoor unit (TCout)c
= Capacity of outdoor unit at design temperature (TCout)d
x Compensation coefcient of pipe length
x Compensation coefcient of frosting/defrosting
3. Decide system capacity.
(8) Calculate
total capacity of indoor units at design temperature (TCin)d.
(9)
System capacity
= the smaller one of (TCout)c and
(TCin)d. • • • • • • • •
(7) or (8)
4. Calculate actual capacity of each indoor unit.
(10) Calculate actual capacity of each indoor unit by dividing system capacity proportionally.
Actual capacity of indoor unit
= (System capacity) x (Rated capacity of indoor unit) / (Total rated
capacity of indoor unit )
= (System capacity) x (TCin)r /
(TCin)r • • • • •
(9) x (1) / (5)
- (02 - 08) -
MODEL
SELECTION
MODEL
SELECTION

Table of Contents

Other manuals for Fujitsu Airstage J-II

Related product manuals