EV KIT3-5.
An EV kit must be required for the compact wall mounted type (EEV external
model) on the liquid pipe side.
EV KIT SELECTION
Model name Application indoor units
UTR-EV09XB AS
E04GACH, AS
E07GACH, AS
E09GACH
UTR-EV14XB AS
E12GACH, AS
E14GACH
A wrong selection could cause improper operation, because the built-in electronic expansion
valve is different.
MODELS REQUIRE EV KIT :
AS
E04GACH, AS
E07GACH, AS
E09GACH, AS
E12GACH, AS
E14GACH
Select the above indoor unit for use in small and, quiet rooms such as hotel or bedroom,
●
where noise would be a distraction.
The other indoor units, do not require an EV kit.
●
DECIDING INSTALLATION LOCATION
Keep the installed piping and wiring length less than 5m.
●
EV kit should be considered to install away from the living quarters, such as above the
●
ceiling.
Install the EV kit where it can be accessed for servicing.
●
EV Kit
Service hole
Indoor unit
5m : Max. (wiring length)
Ceiling
CAUTION
Do not install EV kit in a location with any of the following conditions.
Do not install the kit outdoor. ●
Do not install the kit where the danger of combustible gas leakage. ●
Do not install the kit where near a fire place or other heating appartatus. ●
Do not install the kit where oily smoke, machine oil (i.e. factory),salty enviloment with ●
direct sea breeze.
Do not install the kit where too much of dust. ●
Do not install the kit where corrosive gas such as sulphurous acid gas is generated. ●
Do not install the kit where exposed to rains and direct sunlight. ●
- (06 - 40) -