ADDITIONAL CHARGE CALCULATION2-5.
The outdoor unit is charged refrigerant at the factory.
Additional refrigerant required to be charged on site depending on pipe length.
The additional refrigerant charge amount is calculated according to the following formula.
Round up the calculated result to two decimal places.
CALCULATION OF ADDITIONAL CHARGE REFRIGERANT
1. Calculation of additional amount for outdoor unit
Model HP
b
Factory charged
amount (kg)
AJ
A40LALH 4 4.80
AJ
A45LALH 5 5.30
AJ
A54LALH 6 5.30
Diameter of liquid
pipe (mm)
a
Additional amount for
pipe length (kg/m)
ø6.35 0.021
ø9.52 0.058
2. Calculation of additional amount for pipe length
Total
length of
ø9.52mm
liquid pipe
a :
x 0.058
kg/m
m
kg
Total
length of
ø6.35mm
liquid pipe
a :
x 0.021
kg/m
m
kg
+
A=
=
Total
kg
3. Calculation of additional charge refrigerant
A =
kg
Round up A to 2 decimal place.
4. Factory charged amount
b : Outdoor unit
factory charged amount
kg
B=
5. Total refrigerant amount check
C = A + B =
kg
Note : Check the total refrigerant amount under the following conditions.
Condition Computational formula
Total amount of refrigerant ≤ 15.70kg C ≤ 15.70kg
When total refrigerant amount exceed limitation.
Reduce pipe length for refrigerant system.
Change the refrigerant system configuration.
- (06 - 22) -
SYSTEM
DESIGN
SYSTEM
DESIGN