Note : Specications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
SLIM DUCT / SLIM CONCEALED FLOOR TYPE2-4.
Model name
ARXD04GALH ARXD07GALH ARXD09GALH ARXD12GALH ARXD14GALH
Power source 230V ~, 50Hz
Available voltage range 198 to 264 V
Capacity
Cooling
kW
1.1
2.2 2.8 3.6 4.5
Heating
1.3
2.8 3.2 4.0 5.0
Input power W
40
44 50 54 92
Static pressure range Pa 0 to 90
Standard static pressure Pa 25
Fan
Airow rate
High
m
3
/ h
(l / s)
510
(142)
550
(153)
600
(167)
600
(167)
800
(222)
Med
470 / 400 *1
(131 / 111)
490
(136)
550
(153)
510
(142)
710
(197)
Low
440 / 320 *1
(122 / 89)
440
(122)
480
(133)
450
(125)
610
(169)
Type x Quantity Sirocco × 2
Motor output W 80 81
Sound pressure
level
High
dB(A)
26
28 29 30 34
Med
25 / 21 *1
25 26 27 32
Low
22 / 20 *1
22 24 24 28
Heat exchanger
Length
mm
500
Fin pitch 1.30
Rows x Stages 2 × 14 3 × 14
Face Area m
2
0.15
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit(Aluminium)
Surface
treatment
Hydrophilic coating
Air lter
Type Fungicide type
Net material PP honeycomb
Enclosure
Material galvanized sheet iron
Colour -
Dimensions
(H x W x D)
Net
mm
198 × 700 × 620
Gross 270 × 935 × 770
Weight
Net
kg
17 18
Gross 21 23
Connection
pipe diameter
Liquid (Flare)
mm
ø 6.35
Gas (Flare) ø 12.70
Drain hose VP25 [ø 25(I.D.) ; ø 32(O.D.)]
*1: This value is "cooling operation / heating operation".
- (04 - 17) -
INDOOR