Note : Specications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
Model name ARXD18GALH ARXD24GALH
Power source 230V ~, 50Hz
Available voltage range 198 to 264 V
Capacity
Cooling
kW
5.6 7.1
Heating 6.3 8.0
Input power W 83 122
Static pressure range Pa 0 to 90 0 to 50
Standard static pressure Pa 25
Fan
Airow rate
High
m
3
/ h
(l / s)
940
(261)
1,330
(369)
Med
840
(233)
1,240
(344)
Low
750
(208)
1,100
(306)
Type x Quantity Sirocco × 3 Sirocco × 4
Motor output W 96
Sound pressure
level
High
dB(A)
34 35
Med 32 32
Low 28 29
Heat exchanger
Length
mm
700 900
Fin pitch 1.30
Rows x Stages 3 × 14
Face Area m
2
0.21 0.26
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit(Aluminium)
Surface
treatment
Hydrophilic coating
Air lter
Type Fungicide type
Net material PP honeycomb
Enclosure
Material galvanized sheet iron
Colour -
Dimensions
(H x W x D)
Net
mm
198 × 900 × 620 198 × 1,100 × 620
Gross 270 × 1,135 × 770 270 × 1,335 × 770
Weight
Net
kg
22 26
Gross 27 31
Connection
pipe diameter
Liquid (Flare)
mm
ø 9.52
Gas (Flare) ø 15.88
Drain hose VP25 [ø 25(I.D.) ; ø 32(O.D.)]
- (04 - 18) -
INDOOR
UNITS
INDOOR
UNITS