Note : Specications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
HIGH STATIC PRESSURE DUCT TYPE2-6.
Model name
ARXC36GBTH ARXC45GATH AR XC60GATH ARXC72GBTH ARXC90GBTH
Power source 230 V ~, 50Hz
Available voltage range 198 to 264 V
Capacity
Cooling
kW
11.2 12.5 18.0 22.4 25.0
Heating 12.5 14.0 20.0 25.0 28.0
Input power W 207 715 730 681 819
Static pressure range Pa 0 to 200 100 to 250 100 to 250 0 to 300 0 to 300
Standard static pressure Pa 100 100 100 150 150
Fan
Airow rate
High
m
3
/ h
(l / s)
1,990
(553)
3,500
(972)
3,500
(972)
3,900
(1,083)
4,300
(1,195)
Med
1,680
(467)
3,000
(833)
3,000
(833)
3,300
(917)
4,000
(1,111)
Low
1,330
(369)
2,460
(683)
2,460
(683)
3,000
(833)
3,500
(972)
Type x Quantity Sirocco × 2
Motor output W 197 540 700 x 2
Sound pressure
level
High
dB(A)
42 49 49 47 48
Med 36 45 45 43 46
Low 32 42 42 40 44
Heat exchanger
Length
mm
890 1,250
Fin pitch 1.30 1.45
Rows x Stages 4 × 16 4 × 18
Face Area m
2
0.30 0.50
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit(Aluminium)
Surface
treatment
Hydrophilic coating
Air lter (Option)
Model name UTD-LF60KA
- Type Fungicide type
Net material PP honeycomb
Enclosure
Material galvanized sheet iron
Colour -
Dimensions
(H x W x D)
Net
mm
400 × 1,050 × 500 450 × 1,587 × 700
Gross 460 × 1,230 × 640 520 × 1,750 × 825
Weight
Net
kg
40 46 84
Gross 45 51 100
Connection
pipe diameter
Liquid
mm
ø 9.52(Flare) ø 12.70 (Brazing)
Gas ø 19.05 (Flare) ø 22.22 (Brazing)
Drain hose VP25 [ø 25(I.D.) ; ø 32(O.D.)]
NOTE: ARXC60, ARXC72, and ARXC90 can not be connected in J-II Series and J-IIS Series.
- (04 - 20) -