Note : Specications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
LOW STATIC PRESSURE DUCT / 2-3.
CONCEALED FLOOR TYPE
Model name
ARXB07GALH ARXB09GALH ARXB12GALH ARXB14GALH ARXB18GALH
Power source 230V ~, 50Hz
Available voltage range 198 to 264 V
Capacity
Cooling
kW
2.2 2.8 3.6 4.5 5.6
Heating 2.8 3.2 4.0 5.0 6.3
Input power W 46 55 63 90 96
Static pressure range Pa 0 to 50
Standard static pressure Pa 25
Fan
Airow rate
High
m
3
/ h
(l / s)
370
(103)
440
(122)
590
(164)
800
(222)
890
(247)
Med
310
(86)
370
(103)
500
(139)
750
(208)
810
(225)
Low
280
(78)
340
(94)
450
(125)
700
(194)
730
(203)
Type x Quantity Sirocco × 1 Sirocco × 2
Motor output W 20 18 23 36 42
Sound pressure
level
High
dB(A)
29 31 30 33 36
Med 26 29 28 32 34
Low 24 27 25 30 30
Heat exchanger
Length
mm
410 700
Fin pitch 1.30
Rows x Stages 2 × 14
Face Area m
2
0.12 0.21
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit(Aluminium)
Surface
treatment
Hydrophilic coating
Air lter
Type Anti-mold
Net material PP honeycomb
Enclosure
Material galvanized sheet iron
Colour -
Dimensions
(H x W x D)
Net
mm
217 × 663 × 595 217 × 953 × 595
Gross 324 × 785 × 686 324 × 1,075 × 686
Weight
Net
kg
15 22 23
Gross 20 27 28
Connection
pipe diameter
Liquid (Flare)
mm
ø 6.35 ø 9.52
Gas (Flare) ø 12.70 ø 15.88
Drain hose VP25 [ø 25(I.D.) ; ø 32(O.D.)]
- (04 - 16) -
INDOOR
UNITS
INDOOR
UNITS