Note : Specications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
WALL MOUNTED TYPE2-9.
Model name
AS
A04GACH AS
A07GACH AS
A09GACH AS
A12GACH AS
A14GACH
Power source 230V ~, 50Hz
Available voltage range 198 to 264 V
Capacity
Cooling
kW
1.1 2.2 2.8 3.6 4.5
Heating 1.3 2.8 3.2 4.1 5.0
Input power W 13 17 18 22 34
Fan
Airow rate
High
m
3
/ h
(l / s)
450
(125)
490
(136)
500
(139)
560
(156)
670
(186)
Med
440 / 370* 1
(122 / 103)
450
(125)
450
(125)
480
(133)
490
(136)
Low
420 / 320 *1
(117 / 89)
420 / 370 *1
(117 / 103)
420 / 370 *1
(117 / 103)
420
(117)
420
(117)
Type x Quantity Cross ow × 1
Motor output W 42
Sound pressure
level
High
dB(A)
33 35 36 39 44
Med 32 / 27 *1 33 33 35 37
Low 31 / 22 *1 31 / 27
*1
31 / 27
*1
31 32
Heat exchanger
Length
mm
600
Fin pitch 1.20
Rows x Stages 2×16
Face Area m
2
0.20
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit(Aluminium)
Surface
treatment
Hydrophilic coating
Air lter
Type Antibacterial and Mold proong, Ion deodorization
Net material PP honeycomb
Enclosure
Material Plastic
Colour
WHITE
Approximate colour of MUNSELL N9.25/
Dimensions
(H x W x D)
Net
mm
275 × 790 × 215
Gross 290 × 835 × 345
Weight
Net
kg
9
Gross 12
Connection
pipe diameter
Liquid (Flare)
mm
ø 6.35
Gas (Flare) ø 12.70
Drain hose ø 13.8(I.D.) ; ø 15.8 - ø 16.7(O.D.)
*1: This value is "cooling operation / heating operation".