WIRING SPECIFICATIONS
Use Size Wire type Remarks
Power supply cable
Maximum
1.25
mm
2
60245 IEC 57 or equivalent
1 ø AC100-240 V 50/60 Hz,
2-Wire + ground
(Always ground the unit)
Minimum
0.5 mm
2
Transmission cable
0.33
mm
2
(22AWG)
LEVEL4 (NEMA) non-polar
2-core, twisted pair solid core
Shielded
L
ON
W
ORKS
®
compatible cable
External input /
output cable
0.33
mm
2
(22AWG)
Polar 2-core, Twisted pair
Use shielded cable in
accordance with the regional
cable standard.
Fuse capacity 5 A
SPECIFICATIONS
Model name
UTY-DTG
Power source voltage (V)
1 ø AC 100 - 240
Power source frequency (Hz)
50 / 60
Input Power (W)
22
Display
7.5-inch TFT color LCD (640 × 480 pixels), with Touch panel
LED indicator
Power LED (Green)
External interface
USB 2.0
Transmission line
External Input: (Either emergency stop or batch operation/stop)
(Either Dry contact or Apply voltage can be selected)
External Output: (Operation state, error state)
Reset switch
Usage temperature range (°C)
0 to 40
Usage humidity range (%)
0 to 85 (no condensation)
Storage temperature range (°C)
-20 to 70
Storage humidity range (%)
0 to 85 (no condensation)
Dimensions [H
×
W
×
D] (mm)
260 × 246 × 54
Weight (g)
2150
- (05 - 42) -
CONTROL
SYSTEM
CONTROL
SYSTEM