SYSTEM DIAGRAM
Multiple remote control
z
Up to 4 remote controllers can be used to operate the indoor units.
Master
A
I.U.
Slave SlaveMaster
A B C
I.U.
SlaveMaster
A B
I.U.
Slave Slave SlaveMaster
A B C D
I.U.
A, B, C, D : Remote controller cable. (Refer to Chapter6. 4-4 for detail specications.)
A ≤ 500 m, A+B ≤ 500 m, A+B+C ≤ 500 m, A+B+C+D ≤ 500 m.
NOTE
: Multiple installation method described above is prohibited to combine with UTY-RNK* (3-wired
type) or UTY-RSK* (3-wired type) or UTY-RHK* (3-wired type) and UTY-RNR* (2-wired type) or
UTY-RLR* (2-wired type).
Group control
z
With a single remote controller, up to 16 units can be simultaneously operated.
Master
A
B C D E
I.U. I.U. I.U. I.U.
A, B, C, D, E : Remote controller cable. (Refer to Chapter6. 4-4 for detail specications.)
A+B+C+D+E ≤ 500 m.
- (05 - 59) -