To protect the compressor of the outdoor unit, carefully read and understand the following cautions that may affect
the operation of the compressor before executing the setting.
When performing periodical settings like schedule settings for the following functions, perform the setting to all the
indoor units in the same refrigerant system simultaneously, conforming to the timing restriction described below.
<Corresponding function>
More than 10 minutes must elapse
More than 10 minutes must elapse
· Stop operation
· Set indoor unit forced thermostat
off mode
· Start operation
· Release indoor unit forced
thermostat off mode
Forced thermostat OFF instruction
Only one equipment can send these instructions for each refrigerant system.
When these instructions are sent by multiple equipment, the system may not respond as instructed or may
malfunction.
SPECIFICATIONS
Power supply 1ø AC 208-240 V 50/60 Hz
Input Power (W) 4.5
Dimensions [H × W × D] (mm) 67 × 288 × 211
Weight (g) 1500
Operating environment
z
Temperature(°C)
Operating 0 to 46
Packaged -10 to 60
Humidity (%) Packaged
0 to 95 (RH) ;
No condensation
Transmission specications
z
L
ON
W
ORKS
®
network
Transmission speed 78 kbps
Transceiver FT-X1 (Echelon
®
Corporation)
Transmission form Free topology
Cable
Twisted pair cable (shield)
22AWG equivalent
Network connector One terminal
Terminal resistor None attachment (It attaches at the terminal of a network.)
- (05 - 109) -