POWER SUPPLY CABLE WIRING
Example : Power supply cable wiring.
z
(Using terminal board for indoor units)
Caution
Except for EMERGENCY, never turn off main as well as sub breaker of the indoor units during
operation. It will cause compressor failure as well as water leakage.
First, stop the indoor unit by operating the control unit, converter or external input device and then
cut the breaker.
Make sure to operate through the control unit, converter or external input device.
When the breaker is designed, locate it at a place where the users cannot start and stop in the
daily work.
Regulation of wire size and circuit breaker differs from each locality, please refer in accordance
with regional standard.
Outdoor units
AJ
A54 AJ
A45 AJ
A40
Sub Breaker
Sub Breaker
Sub Breaker
32A
32A
32A
Power cable
6mm
2
Power cable
6mm
2
Power cable
6mm
2
Sub Breaker
Terminal board
Terminal board
Sub Breaker
20A
20A
Indoor unit power supply
1ø 50Hz 230V
Outdoor unit power supply
1ø 50Hz 230V
Power cable
2.5mm
2
Indoor
units
Indoor
units
Connected within
refrigerant system.
Total MCA ≤ 15 (A).
Total Sub Breaker ≤ Main Breaker
- (06 - 48) -